2016-02-02 11:14:42BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120685
 ADD: 2000 PRESIDENTIAL WAY # 1906
 CONT: AMENGUAL ELEC.
 TEL: 954-410-6364
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: TUES. FEB. 02/2016
 ACTION: DENIED
  
 1) COMPLIED., BUILDING TYPE IS A 1-A.
  
 2) 2ND REQUEST. THE COVERSHEET A-0.01 INDICATES NEW
 TILE FLOORS THROUGH OUT THE APARTMENT. PLEASE PROVIDE
 TEST REPORTS NOT THE MANUFACTURERS SPEC. SHOWING
 COMPLIANCE WITH:
  
 2A) 2ND REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) 2ND REQUEST. FLAME SPREAD- FBC-B 2014 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  