Plan Review Notes For Permit 15120665 |
Permit Number |
15120665 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-12-21 09:16:19 | RESIDENTIAL (R3) RE-ROOF REVISION, BUILDING REVIEW | | COMMENTS. | | CODE: 2010 FBC-RESIDENTIAL | | | | 1- FLAT ROOF NOA 14-0611.01 SUBMITTED EXPIRED ON | | 11/06/2015. NEED TO PROVIDE CURRENT NOA. FAC | | 61G20-3.002(33). | | | | 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM NOA | | SUBMITTED IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE | | WITH THE DESIGN PRESSURES OF SEC. R301 OF 2010 | | FBC-RESIDENTIAL. | | | | 3- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | REQUIRED BY GENERAL LIMITATION #7 ONLAST PAGE OF NOA | | SUBMITTED. THIS CALCULATIONS ARE REQUIRED TO MEET THE | | DESIGN PRESSURES OF SEC. R301. | | NOTE: ASSEMBLIES FROM NOA SUBMITTED THAT ARE LIMITED BY | | GENERAL LIMITATION #9 CAN NOT BE USED BECAUSE THEY | | DON'T MEET THE DESIGN PRESSURES OF SEC. R301. | | | | IF YOU HAVER ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|