Plan Review Notes
Plan Review Notes For Permit 15120665
Permit Number 15120665
Review Stop B
Sequence Number 1
Notes
Date Text
2015-12-21 09:16:19RESIDENTIAL (R3) RE-ROOF REVISION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC-RESIDENTIAL
  
 1- FLAT ROOF NOA 14-0611.01 SUBMITTED EXPIRED ON
 11/06/2015. NEED TO PROVIDE CURRENT NOA. FAC
 61G20-3.002(33).
  
 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM NOA
 SUBMITTED IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 3- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ONLAST PAGE OF NOA
 SUBMITTED. THIS CALCULATIONS ARE REQUIRED TO MEET THE
 DESIGN PRESSURES OF SEC. R301.
 NOTE: ASSEMBLIES FROM NOA SUBMITTED THAT ARE LIMITED BY
 GENERAL LIMITATION #9 CAN NOT BE USED BECAUSE THEY
 DON'T MEET THE DESIGN PRESSURES OF SEC. R301.
  
 IF YOU HAVER ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]