Plan Review Notes For Permit 15120656 |
Permit Number |
15120656 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-12-20 10:15:48 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL | | | | DENIED | | | | THE INSTALLATION MANUAL PROVIDED FROM THE FBC WEBSITE | | FOR FL 11903.1 ON PAGE V-2 ITEM #8 INDICATES FASTENER | | SPACING ALONG THE LENGTH OF THE PANEL IS FOUND ON PAGE | | V-5. PAGE V-5 HOWEVER, DOES NOT CONTAIN INFORMATION ON | | FASTENER SPACING. PLEASE NOTE, I REVIEWED THE | | EVALUATION REPORT PREPARED BY TERRANCE E. WOLFE, P.E. | | FOR THE PRODUCT ONLINE AND FOUND HE PROVIDES THAT 1'-0" | | O.C. SPACING IS GOOD FOR -146 PSF AND 2'-0" O.C. | | SPACING IS GOOD FOR -74.75 PSF. PLEASE PROVIDE THE | | PROPOSED FASTENER SPACING ALONG THE LENGTH OF THE | | PANEL." | | | | PLEASE NOTE, I HAVE CONTACTED FBC STAFF FOR ASSISTANCE. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | | | |
|