2016-06-07 11:09:11 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15120536 |
| ADD: 2745 OKEECHOBEE BLVD. |
| CONT: HEDRICK BROTHERS |
| TEL: 561-568-8931 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 3RD REVIEW |
| DATE: TUES. JUNE 07/ 2016 |
| ACTION: BUILDING PROVISO |
| |
| 1) PROVISO: SHEET 035-A.1.1.1A & 038-A1.1.1.1D BOTH |
| SHOW THE USE OF PLATFORM LIFTS. A REVISION IS REQUIRED, |
| DELETING THE PLATFORM LIFT IN COMPLIANCE WITH THE 2014 |
| FBC-ACCESSIBILITY CODE 206.7 NOT ALLOWED IN NEW |
| CONSTRUCTION. |
| |
| 2) PROVISO: 090-A4-4 DETAILS 1 & 2 FLOOR STRUCTURAL |
| MEMBERS ARE 34 INCH DOUBLE T CONCRETE JOIST. THIS WOULD |
| PROVIDE AN 8FT.-8 IN. CLEAR SPACE BENEATH THE JOIST, |
| DEPENDING ON THE LAYOUT OF THE RAINWATER HORIZONTAL |
| RUNS AND FIRE SPRINKLER LAYOUT WHICH HAS NOT YET BEEN |
| PROVIDED.2014 FBC-B 406.4.1. |
| |
| 3) PROVISO: 2014 FBC-B SECTION [F] 406.6.3 AUTOMATIC |
| SPRINKLER SYSTEM. AN ENCLOSED PARKING GARAGE SHALL BE |
| EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 903.2.10. |
| |
| 4) PROVISO: DEFERRED SUBMITTAL . DOOR TYPE (N) SHOW |
| THEY ARE A HORIZONTAL BI-PARTING DOOR. SHEET 113-A8-0 |
| INDICATES A DOOR TYPE (N) BUT DOES NOT INDICATE TO |
| WHICH CODE SECTION THE DOORS ARE COMPLY 1008.1.4.2 |
| POWER OPERATED DOORS OR 1008.1.4.3 HORIZONTAL SLIDING |
| DOORS OR HOW MUCH FORCE IS TO BE APPLIED TO SET THE |
| DOOR IN MOTION. DOORS SHALL BE OPENABLE BY A SIMPLE |
| METHOD FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR |
| EFFORT, HOW WILL THIS BE ACCOMPLISHED. |
| |
| 5) PROVISO/ DEFERRRED SUBMITTAL. SHEET 100-A6-2 |
| SKYLIGHT GLAZING IS GOING TO COMPLY WITH THE 2014 FBC-B |
| 2405.2 ALLOWABLE GLAZING MATERIALS AND LIMITATIONS. |
| 2405.5 UNIT SKYLIGHTS AND TUBULAR DAYLIGHTING DEVICES. |
| |
| 6) PROVISO: DEFERRED SUBMITTALS. PLEASE SUBMIT PRODUCT |
| APPROVALS TO COMPLY WITH: 2014 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING, AND |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 7) PROVISO: DEFERRED SUBMITTALS. 2014 FLORIDA BUILDING |
| CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.4.2 |
| DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, |
| DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF |
| THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE |
| APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |