2016-04-19 11:07:57PLUMBING COMMENTS:
  
 1. SHT. P1.1 THE TRENCH DRAIN SHOWS A SECOND PIPE
 CONNECTED TO IT NOT TIED TO OIL SEPARATOR .
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 2. ORIGINAL COMMENT STATES SHT.A2.0 - DETAIL #1 - THE
 DOORS TO RESTROOMS #213 & 214 CANNOT SWING INTO THE
 CLEA R FLOOR SPACE FOR THE LAVATORIES. 2014 FBC-ACCESS.
 SEC.603.2.3. (SEE EXCEPTION #2). 2ND REVIEW YOU SHOW
 COMPLIANCE WITH EXCEPTION IN BATHROOM 213 BUT NO IN 214
 .
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 3.SHT. A2.1 - DETAIL #1 - SHOW THE INSIDE CLEAR
 DIMENSION OF THE ACCESSIBLE STALL IN THE WOMEN'S
 RESTROOM. MINIMUM WIDTH IS 85 INCHES. 86 INCHES ALLOWS
 FOR TOLERANCE. ALSO, SHOW THE FIXTURE CLEARANCE OF THE
 WATER CLOSET IN THE STALL FROM THE SIDE WALL TO THE
 CENTERLINE OF THE WATER CLOSET. 2ND REQUEST
  
 4. SHT. A10.1 THE TOP OF URINAL SCREEN SHOWS 56IN.
 ABOVE FF IT SHALL BE A MIN. OF 60IN.
 PER FBC SEC. 1210.3.2
  
 5. SHT. P1.1 RM # 171
 (A) PROVIDE PIPING DIAGRAM FOR M OIL MANAGEMENT
 CONTROLLER
 (B) THE TANKS THAT ARE LABELED M ARE THEY FOR STORAGE
 OF OIL MEASURED IN GALLONS PLEASE CLARIFY.
 (C) WHAT ARE H AND K FOR PLEASE CLARIFY.
 (D) IT APPEARS THAT THE PARTS WASHER IS LABELED AS M
 FOR OIL MANAGEMENT CONTROLLER PLEASE CLARIFY
 (E) PROVIDE PIPING DIAGRAM FOR BLOWER LABELED P.
 PER WPB AMEND. TO FBC SEC. 107.2.1
  
 6. THE STACK FOR THE SINK ON THE 5TH FLOOR IS SHOWN ON
 P1.3 AS A 4IN. ON SHT. P2.1 IT IS SHOWN AS 2IN.
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 7. SHT. P0.1 THE SPECS GIVEN FOR OIL SEPARATOR DO NOT
 COMPLY WITH FBC PL SEC 1003.4.2.1.
 PROVIDE MANUFACTURE SPECS THAT COMPLY WITH FBC PL SEC
 1003.4.2.1.
  
 8. SHT. P0.3 THE CALCULATION GIVEN FOR OIL SEPARATOR DO
 NOT COMPLY WITH FBCPL SEC 1003.4.2.2 IT APPEARS THAT
 YOU MIGHT HAVE USED CALCULATION FOR SIZING A GREASE
 INTERCEPTOR.
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 9. SHT. P1.2 SHOW A PLAN NOTE IN THE AREA RM # 115 AND
 117 THAT INDICATES A WATER HEATER AND MOP SINK .
 PLEASE CLARIFY PER WPB AMEND. TO FBC SEC. 107.2.1
  
 10. THE DIGITAL SIGNATURES ARE INVALID ON PLUMBING
 PAGES THEY SHALL COMPLY WITH FAC 61G15-23.003
  
  
 2ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER