2016-03-31 08:00:002ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS:
  
 THE BELOW COMMENTS AS PREVIUOSLY STATED WILL REQUIRE
 AHJ APPROVAL, PLEASE MAKE ARRANGEMENTS TO CONTACT
 ROBERT BROWN (BO) OR DOUG HARVEY (ABO)
 ALL OTHER COMMENTS ADDRESSED EXCEPT THE BELOW INITIAL
 REVIEW COMMENTS
  
  
 13. SHEET 3.1- PLEASE NOTE THAT ALL MAIN DISCONNECTS
 MUST BE GROUPED AT THE SAME LOCATION PER NEC 230.72A.
 ALSO NEC 230.2 REQUIRES THAT BUILDINGS BE SUPPLIED BY
 ONLY ONE SERVICE UNLESS PERMITTED BY NEC 230.2A THROUGH
 230.2D. THE ARRANGEMENTS OF THE ELECTRICAL SERVICE
 SHOWN PER PHASING INTENT MUST BE APPROVED BY SPECIAL
 PERMISSION OF THE AHJ. PROVIDE REQUEST IN WRITING WHICH
 IS SUBJECT TO APPROVAL.
 14. SHEET 3.2- RISER DIAGRAM AT THIS TIME WILL NEED TO
 BE REVISITED PENDING APPROVAL AS NOTED IN COMMENT #13.
 SEE ABOVE.
 15. SHEETS 4.1 THROUGH 4.4- PANEL SCHEDULES AT THIS
 TIME WILL NEED TO BE REVISITED PENDING APPROVAL AS
 NOTED IN COMMENT #13. SEE ABOVE.
 16. SHEET 5.3- ELECTRICAL ROOMS MUST COMPLY WITH NEC
 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF
 THE WORKING SPACE. SHOW TWO MEANS OF EXIT FOR ROOM 170.
 ALSO NEC 110.26C3 REQUIRES PERSONNEL DOORS TO BE
 EQUIPPED WITH PANIC HARDWARE AND OPEN IN THE DIRECTION
 OF EGRESS. A NOTE WILL SUFFICE.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717