Plan Review Notes
Plan Review Notes For Permit 15120536
Permit Number 15120536
Review Stop B
Sequence Number 2
Notes
Date Text
2016-04-15 09:35:39BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120536
 ADD: 2745 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: 561-568-8931
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: THURS. APRIL 14/ 2016
 ACTION: DENIED
  
 1) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 7/1/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $500,000. PER CITY OF WEST
 PALM BEACH ORDINANCE NO. 4504-14, AND CITY OF WEST PALM
 BEACH CODE OF ORDINANCES, ARTICLE V, ART IN PUBLIC
 PLACES, SECTION 78-123(A) AND SECTION 78-126(A), THE
 ART ASSESSMENT IS 1% OF THE TOTAL PROJECT CONSTRUCTION
 COST.
  
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
  
 2) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 THRESHOLD BUILDING FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) COMPLIED. 109.3.6.1 WRITTEN THRESHOLD INSPECTION
 PLAN.
  
 2B) 2ND REQUEST, THE THRESHOLD INSPECTION FORMS ARE TO
 BE SIGNED BY ALL PARTIES BEFORE SUBMITTAL TO THE
 BUILDING DEPARTMENT. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED
 OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND
 RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE. CONTACT KEN
 CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6666 FOR FURTHER INFORMATION BEFORE THE PERMIT
 MAY BE ISSUED.
  
 2C) COMPLIED. 663 FLORIDA STATUTE.
  
 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
  
 2E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) NOTICE ONLY: FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
  
 2G) INFORMATIONAL. PLEASE CALL THE CITY OF WEST PALM
 BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2H) INFORMATIONAL. 109.3.6 THRESHOLD BUILDINGS,
 OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26.
 ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3) 2ND REVIEW. SHEET 001-INDEX INDICATES SHEET 033-A0.1
 IS MISSING, AND IS NOT PART OF THIS SUBMITTAL. A
 THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) 2ND REQUEST. THE SUBMITTED DOCUMENT IS SIGNED AND
 SEALED AS A PAPER DOCUMENT, THERE IS NO ELECTRONIC
 SIGNATURE TO THIS DOCUMENT. THE ENGINEER HAS 2 OPTIONS,
 EITHER COMPLY WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS OR SUBMIT 1 ORIGINAL PAPER
 DOCUMENT SIGNED AND SEALED.
  
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) SHEET 027-LS-1E:
  
 5A) COMPLIED.
  
 5B) 2ND REQUEST. SUBMITTED A MANUFACTURERS BROCHURE
 FROM GARAVENTA LIFT. THE BROCHURE WAS PRINTED IN
 CANADA, THE LIFT MAYBE MADE IN CANADA AND NOT HAVE A
 ASME A18.1 LISTING. THE SERVICE VESTIBULE SHOWS THE USE
 OF A PLATFORM LIFT, PLEASE PROVIDE THE MANUFACTURERS
 SHOP DRAWINGS AND OR SPEC SHEET THAT SHOWS THE LIFT
 COMPLIES WITH ASME A18.1 (FBC-ACCESSIBILITY CODE
 410.1).
  
 5C) COMPLIED. RECEIVING ROOM 163, EXIT DISCHARGE TO A
 PUBLIC WAY.
  
 5D) COMPLIED. NO MEZZANINE IN THE PARTS STORAGE LEVEL.
  
 5E) COMPLIED.
 6-8) COMPLIED.
  
 9) 2ND REQUEST. SHEET 145-S1.1A IN THE BOTTOM RIGHT
 SHOWS A KEY FOUNDATION PLAN FOR THE FOUNDATION. THE KEY
 PLAN DOES NOT IDENTIFY THE FOUNDATION BEHIND THE
 BUILDING LABELED 1. PLEASE PROVIDE WHERE THIS PLAN CAN
 BE LOCATED.
  
 10-11) COMPLIED.
  
 12) 2ND REQUEST. PLEASE SHOW THE STRETCHER REQUIREMENTS
 WITHIN THE CAB. THE CONCRETE WALL OPENING AND THE CAB
 OPENING DOES NOT LINE UP, MAKING THE TURN INTO THE CAB
 APPEAR VERY TIGHT FOR CODE COMPLIANCE.
 SHEET 037-A1-1-1C NOR THE SHEET 109-A7-1 SHOW THE CAB
 OF ELEVATOR # 1 ACCOMMODATES THE AMBULANCE STRETCHER
 REQUIREMENTS OF FBC-B 3002.4.
  
 13) COMPLIED.
  
 14A) COMPLIED. GENERATOR IS BEING ADDED TO THE PROJECT.
  
 14B) COMPLIED.
  
 14C) PROVISO: 090-A4-4 DETAILS 1 & 2 FLOOR STRUCTURAL
 MEMBERS ARE 34 INCH DOUBLE T CONCRETE JOIST. THIS WOULD
 PROVIDE AN 8FT.-8 IN. CLEAR SPACE BENEATH THE JOIST,
 DEPENDING ON THE LAYOUT OF THE RAINWATER HORIZONTAL
 RUNS AND FIRE SPRINKLER LAYOUT WHICH HAS NOT YET BEEN
 PROVIDED.2014 FBC-B 406.4.1.
  
 15)COMPLIED
  
 16-17) PROVISO: SHEET 026-LS-0-. FULLY SPRINKLERED
 BUILDING. DEFERRED SUBMITTAL.
  
 18) COMPLIED.
  
 19) 2ND REQUEST. THERE IS NO REVISED SHEET. . THIS
 COMMENT IS COMMON FOR ALL FLOORS. SHEET 055-A1-2-B THE
 FLOOR INDICATES THE ELEVATION OF THE LEVEL FLOOR AT
 38.0 FEET. THE PLANS DO SHOW WHAT APPEARS TO BE FLOOR
 DRAINS BUT THE DIFFERENCE IN ELEVATION IS NOT MARKED ON
 THE PLANS NOR IS THERE ANY NOTES ON THE PLANS
 INDICATING THE DIFFERENCE IN ELEVATION. PLEASE PROVIDE
 COMPLIANCE WITH THE 2014 FBC-B 406.4.5 FLOOR SURFACE.
 THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR
 OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE
 MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN
 VEHICLE ENTRY DOORWAY.
  
 20) SEE COMMENTS FROM THE MECHANICAL REVIEWER 2ND
 REVIEW. PORTIONS OF THE 1ST FLOOR AND 2ND FLOOR ARE
 CONSIDERED AN ENCLOSED PARKING GARAGE, PLEASE IDENTIFY
 WHERE IN EITHER THE ARCHITECTURAL SHEETS OR THE
 MECHANICAL SHEETS COMPLIANCE WITH 2014 FBC-B 406.6.2
 VENTILATION. A MECHANICAL VENTILATION SYSTEM SHALL BE
 PROVIDED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL.
  
 21) PROVISO: 2014 FBC-B SECTION [F] 406.6.3 AUTOMATIC
 SPRINKLER SYSTEM. AN ENCLOSED PARKING GARAGE SHALL BE
 EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.2.10.
  
 22) SEE COMMENTS FROM THE MECHANICAL REVIEWER. PLEASE
 PROVIDE WHERE COMPLIANCE WITH FBC-B SECTION 406.8.2
 VENTILATION. REPAIR GARAGES SHALL BE MECHANICALLY
 VENTILATED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, MECHANICAL. THE VENTILATION SYSTEM SHALL BE
 CONTROLLED AT THE ENTRANCE TO THE GARAGE.
  
 23) PROVISO: 2014 FBC-B SECTION 406.8.6 AUTOMATIC
 SPRINKLER SYSTEM. A REPAIR GARAGE SHALL BE EQUIPPED
 WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.2.9.1.
  
 24) COMMENT IS NEW FROM THE ORIGINAL COMMENT!!!!! SHEET
 038-A1-1-1D. NEXT TO STAIR 128 THE PLANS INDICATE THE
 USE OF A PLATFORM LIFT. THIS IS NEW CONSTRUCTION PLEASE
 LOOK AT THE SCOPING REQUIREMENT FOR THE LIMITED USE OF
 PLATFORM LISTS ON AN ACCESSIBLE ROUTE IN NEW
 CONSTRUCTION UNDER 2014 FBC-B 206.7.
  
 25) SHEETS 035-A1.1.1A THROUGH 040-A1.1.1F, AND SHEET
 113-A8.0 DOOR SCHEDULE:
  
 25A) PROVISO: DEFERRED SUBMITTAL . DOOR TYPE (N) SHOW
 THEY ARE A HORIZONTAL BI-PARTING DOOR. SHEET 113-A8-0
 INDICATES A DOOR TYPE (N) BUT DOES NOT INDICATE TO
 WHICH CODE SECTION THE DOORS ARE COMPLY 1008.1.4.2
 POWER OPERATED DOORS OR 1008.1.4.3 HORIZONTAL SLIDING
 DOORS OR HOW MUCH FORCE IS TO BE APPLIED TO SET THE
 DOOR IN MOTION. DOORS SHALL BE OPENABLE BY A SIMPLE
 METHOD FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR
 EFFORT, HOW WILL THIS BE ACCOMPLISHED.
  
 25B) COMPLIED
  
 26) PROVISO/ DEFERRRED SUBMITTAL. SHEET 100-A6-2 PLEASE
 PROVIDE HOW THE SKYLIGHT GLAZING IS GOING TO COMPLY
 WITH THE 2014 FBC-B 2405.2 ALLOWABLE GLAZING MATERIALS
 AND LIMITATIONS.
 2405.5 UNIT SKYLIGHTS AND TUBULAR DAYLIGHTING DEVICES.
 UNIT SKYLIGHTS AND TUBULAR DEVICES SHALL BE TESTED AND
 LABELED AS COMPLYING WITH AAMA/WDMA/CSA 101/I.S./A440.
 THE LABEL SHALL STATE THE NAME OF THE MANUFACTURER, THE
 APPROVED LABELING AGENCY, THE PRODUCT DESIGNATION AND
 THE PERFORMANCE GRADE RATING AS SPECIFIED IN
 AAMA/WDMA/CSA 101/I.S.2/ A440. IF THE PRODUCT
 MANUFACTURER HAS CHOSEN TO HAVE THE PERFORMANCE GRADE
 OF THE SKYLIGHT RATED SEPARATELY FOR POSITIVE AND
 NEGATIVE DESIGN PRESSURE, THEN THE LABEL SHALL STATE
 BOTH PERFORMANCE GRADE RATINGS AS SPECIFIED IN
 AAMA/WDMA/ CSA 101/I.S.2/A440 AND THE SKYLIGHT SHALL
 COMPLY WITH SECTION 2405.5.2. IF THE SKYLIGHT IS NOT
 RATED SEPARATELY FOR POSITIVE AND NEGATIVE PRESSURE,
 THEN THE PERFORMANCE GRADE RATING SHOWN ON THE LABEL
 SHALL BE THE PERFORMANCE GRADE RATING DETERMINED IN
 ACCORDANCE WITH AAMA/WDMA/CSA 101/ I.S.2/A440 FOR BOTH
 POSITIVE AND NEGATIVE DESIGN PRESSURE AND THE SKYLIGHT
 SHALL CONFORM TO SECTION 2405.5.1.
  
 27) 2ND REQUEST. SHEET 140-S0.1 . 0143_1.S0.4 &
 143.1_S).4A.
 PLEASE PROVIDE WHERE THE MEAN ROOF HEIGHT FOR THE
 BUILDING IS GIVEN? 2014 FBC-B TABLE 1609.7(2) I CAN
 UNDERSTAND THERE WILL BE ONE SET OF CALCULATIONS UNDER
 COMPONENTS AND CLADDING FOR THE ENCLOSED PORTION OF THE
 BUILDING, BUT WOULDN?T IT BE TAKEN AT THE TOP OF THE
 PARKING GARAGE? THIS IS ONE BUILDING, ONE MEAN ROOF
 HEIGHT. THE ISSUE IS THE DIFFERENT COEFFICIENTS USED
 FOR AN OPEN BUILDING AND ENCLOSED BUILDING. SO WOULDN?T
 THERE BE 2 SCENARIOS A PORTION OF THE BUILDING AS OPEN
 AND A PORTION OF THE BUILDING ENCLOSED?
  
 THE 2ND ISSUE WITH THE UPPER PORTION OF THE CHARTS, FOR
 EXAMPLE THE UPPER LEFT CHARTS THE GROSS ALLOWABLE WIND
 LOADS MAIN ROOF ROOFING MATERIALS IS LISTED WITH
 COMPONENTS AND CLADDING. THE NEXT CHART DOWN THE CHART
 INDICATES NET ALLOWABLE WIND LOADS MAIN ROOF JOIST AND
 STILL LISTED AS COMPONENTS AND CLADDING. JOIST ARE NOT
 COMPONENTS AND CLADDING BUT PART OF THE MWFRS (MAIN
 WIND FORCE RESISTING SYSTEM). THIS OCCURS 4 TIMES ON
 THIS PAGE WHERE IT APPEARS TO BE A DIFFERENCE IN THE
 CORRECT TERMINOLOGY AND ASSOCIATED PRESSURES. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED AND APPEARS TO BE A
 TYPO IN REGARDS TO TERMINOLOGY.
  
 COMMENT 1ST ROUND COMMENTS. SHEET 140-S0.1 STRUCTURAL
 SPECIFICATION NOTES MISC. NOTE # 6 IS THE WIND DESIGN
 CRITERIA, PLEASE ALSO PROVIDE AT WHAT MEAN ROOF HEIGHT
 IS THE PRESSURES FOUND ON SHEET 143-S0.4 TAKEN? UNTIL
 THE MEAN ROOF HEIGHT IS GIVEN THE PRESSURES CANNOT BE
 VERIFIED. 2014 FBC-B TABLE 1609.7(2) ADJUSTMENT FACTORS
 FOR HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR
 THE BUILDING. MEAN ROOF HEIGHT. THE AVERAGE OF THE ROOF
 EAVE HEIGHT AND THE HEIGHT TO THE HIGHEST POINT ON THE
 ROOF SURFACE, EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR
 ROOF ANGLE OF LESS THAN OR EQUAL TO 10 DEGREES (0.18
 RAD).
  
  
 28) 2ND REQUEST. PLEASE PROVIDE THE PRESSURES FOUND ON
 SHEET 143-S0.4 IN VASD SINCE ALL OF THE PRODUCT
 APPROVALS ARE IN VASD. THE INSPECTORS ON SITE WILL BE
 LOOKING FOR THE PRESSURES ON THE S0,4 SHEET TO BE
 INLINE WITH THE PRODUCT APPROVALS. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 29A) PROVISO: DEFERRED SUBMITTALS.
 PLEASE SUBMIT PRODUCT APPROVALS TO COMPLY WITH: 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING, AND
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 29B) PROVISO: DEFERRED SUBMITTALS.
 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 29C) PROVISO: DEFERRED SUBMITTALS. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 30) COMPLIED.
  
 31) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 32) PLANS MISSING THE ELECTRONIC SIGNATURES ON THE
 CIVEL SHEETS AND SITE PLANS, ALSO REVIEWED
 ARCHITECTURAL AND STRUCTURAL.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 33) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  