Date |
Text |
2016-01-19 09:49:15 | 1) PROVIDE MATCH LINES FOR THE PLUMBING PLAN VIEW |
| DRAWINGS. IT IS DIFFICULT TO FOLLOW THE CONTINUATION OF |
| THE PLUMBING SYSTEM FROM ONE SHEET TO THE NEXT.WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 2) CLARIFY THE OCCUPANCY TYPE THAT YOU ARE USING TO |
| CALCULATE THE REQUIRED PLUMBING FIXTURES FOR THE |
| PORSCHE & BENTLEY AREAS. |
| 3) THE ARCHITECTURAL PLANS HAVE THE DIFFERENT AREAS |
| LABELE "A - F" AND THE PLUMBING PLANS ARE LABELED BY |
| THE AREA NAME ( PORSCHE-SOUTH, PORSCHE-NORTH, ROLLS |
| ROYCE/BENTLEY ETC.). IT IS EXTREMELY DIFFICULT TO |
| REVIEW THESE PLANS WITHOUT CORRELATING NAMING |
| CONVENTIONS. PLEASE ATTEMPT TO CORRELATE THE |
| IDENTIFICATION OF THESE PLANS IN A MANNER THAT MAKES IT |
| EFFICIENT TO PERFORM A COMPREHENSIVE REVIEW. |
| 4) THE TRENCH DRAINS LOCATED IN THE DETAIL AREA #166 |
| SHALL DISCHARGE TO THE OIL INTERCEPTOR PER THE 2014 |
| FBC-PLUMBING SEC.1003.4.2.2. |
| 5) SHT. A1.1.1E - LOCKER ROOMS #125 & #126 SHOWS A |
| HANDICAPPED ACCESSIBLE TOILET COMPARTMENT WITH A |
| LAVATORY IN IT BUT NO WATER CLOSET. CLARIFY. 2014 |
| FBC-ACCESS. SEC.213.3.1 & 604.8.1. |
| 6) SHT. A1.1.1E - LOCKER RM. 3126 - SHOWS THE DOOR FOR |
| THE ACCESSIBLE STALL SWINGING INTO THE CLEAR FLOOR |
| SPACE FOR WHAT APPEARS TO BE AN ACCESSIBLE URINAL. THE |
| DOOR CANNOT SWING INTO THE CLEAR FLOOR SPACE FOR THE |
| FIXTURE PER 2014 FBC-ACCESS.SEC.603.2.3. |
| 7) SHT. A1.2.1 - THE BREAK ROOM SINK IN ROOM #209 SHALL |
| COMPLY WITH 2014 FBC-ACCESS. SEC.212 & 606. |
| 8) SHT. A1.5.1 - TOILET ROOM # 500A - SHOW THE WIDTH OF |
| THE TOILET ROOM ON DETAIL #2. THE MINIMUM WIDTH IS 85 |
| INCHES. 86 INCHES ALLOWS FOR TOLERANCE. |
| 9).SHOW THE INSIDE CLEAR DIMENSIONS (LXW) OF ALL SINGLE |
| USER TOILET ROOMS. WPB AMEND. TO FBC SEC. 107.2.1. |
| 10) SHT. A2.0 - DETAILS #2 & #4 - IDENTIFY THE |
| HANDICAPPED ACCESSIBLE URINAL IN BOTH RESTROOMS. COMPLY |
| WITH 2014 FBC - ACCESS. SEC.605. |
| 11) SHT. A2.0 - SHOW THE FIXTURE CLEARANCE DIMENSION |
| FROM THE CENTERLINE OF THE ACCESSIBLE WATER CLOSET TO |
| THE SIDE WALL. COMPLY WITH 2014 FBC-ACCESS. SEC. 604.2. |
| 12) SHT.A2.0 - DETAIL #1 - THE DOORS TO RESTROOMS #213 |
| & 214 CANNOT SWING INTO THE CLEAR FLOOR SPACE FOR THE |
| LAVATORIES. 2014 FBC-ACCESS. SEC.603.2.3. (SEE |
| EXCEPTION #2). |
| 13) SHT. A2.0 - SHOW THE FIXTURE CLEARANCES OF THE |
| URINALS ON SHT. A2.0, DETAIL #2 AND ALSO DETAIL #4. |
| .COMPLY WITH 2014 FBC-PLUMBING, SEC.405.3.1. |
| 14) SHT. A2.1 - SHOW THE FIXTURE CLEARANCE FOR THE |
| URINALS IN THE ENLARGED STAFF LOCKERS/RESTROOMS, DETAIL |
| #2. COMPLY WITH 2014 FBC-PLUMBING SEC. 405.3.1. |
| 15) SHT. A2.0 - DETAIL #4 - THE DRINKING FOUNTAINS |
| SHALL CCOMPLY WITH 2014 FBC-ACCESS. SEC.307.2 FOR |
| PROTRUDING OBJECTS. |
| 16) SHT. A2.1 - DETAIL #2 - SHOW THE REQUIRED TURNING |
| SPACE IN THE MEN'S & WOMEN'S RESTROOMS PER THE 2014 |
| FBC- ACCESS. SEC.304.3.1. |
| 17) SHT. A2.1 - DETAIL #1 - SHOW THE INSIDE CLEAR |
| DIMENSION OF THE ACCESSIBLE STALL IN THE WWOMEN'S |
| RESTROOM. MINIMUM WIDTH IS 85 INCHES. 86 INCHES ALLOWS |
| FOR TOLERANCE. ALSO, SHOW THE FIXTURE CLEARANCE OF THE |
| WATER CLOSET IN THE STALL FROM THE SIDE WALL TO THE |
| CENTERLINE OF THE WATER CLOSET. |
| 18) SHT. A10.1 - THE URINAL SCREEN SHALL EXTEND NOT |
| LESS THAN 60 INCHES ABOVE THE FINISH FLOOR.2014 FBC |
| SEC. 1210.3.2. |
| 19) SHT. A10.1 - SHOW THE REQUIRED CLEAR FLOOR SPACE |
| UNDER THE LAVATORY IN DETAIL #7. COMPLY WITH 2014 |
| FBC-ACCESS. SEC.305, 306. |
| 20) SHT.A10.3 - DETAILS #7 & #8 - THE HEIGHT OF THE |
| WATER CLOSET IS SHOWN AS 15 INCHES ABOVE THE FINISH |
| FLOOR. THE HEIGHT OF THE ACCESSIBLE WATER CLOSET SHALL |
| BE BETWEEN 17" & 19 " ABOVE THE FINISH FLOOR. 2014 FBC- |
| ACCESS. SEC.604.4. |
| 21) SHT. A10.7 - DETAIL #6 - THE URINAL LIP IS SHOWN AS |
| 1'-7" ABOVE THE FINISH FLOOR. IF THIS IS A HANDICAPPED |
| URINAL, THE MAX. HEIGHT TO THE URINAL LIP SHALL BE 17 |
| INCHES. FBC-ACCESS. SEC. 605.2. |
| 22) SHT.A10.7 - DETAIL # 16 - THE URINAL LIP IS SHOWN |
| AS 1'-7" ABOVE THE FINISH FLOOR. IF THIS IS A |
| HANDICAPPED URINAL, THE MAX. HEIGHT TO THE URINAL LIP |
| SHALL BE 17 INCHES. FBC-ACCESS. SEC. 605.2. |
| 23) SHT. P1.1 - IDENTIFY ALL THE EQUIPMENT & TANKS IN |
| ROMM #171. WPB AMEND. TO FBC SEC.107.2.1. |
| 24) SUBMIT A PIPING RISER FOR THE COMPRESSED AIR |
| SYSTEM.WPB AMEND. TO FBC SEC.107.2.1. |
| 25) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW. WPB |
| AMEND. TO FBC SEC.107.2.1. |
| 26) CLEARLY SHOW THE DRAIN LINES FROM THE ELEVATOR |
| SUMPS TO THE OIL WASTE SYSTEM ON THE PLUMBING RISER.WPB |
| AMEND. TO FBC SEC.107.2.1. |
| 27) SHT.P2.2 - MEN'S & WOMEN'S TOILET ROOMS #154 & #155 |
| - THE CIRCUIT VENT SHALL BE LOCATED BETWEEN THE THE TWO |
| MOST UPSTREAM FIXTURE DRAINS. AS DRAWN, THE VENT IS |
| LOCATED DOWNSTREAM OF THE TWO MOST UPSTREAM WATER |
| CLOSETS.2014 FPC SEC.914.2. |
| 28) SHT. P2.1 - SANITARY RISER #2 - TECH RESTROOMS - |
| SIZE THE VENTS FOR THE URINALS. |
| 29) SHT. P2.1 - RISER #1 - ROLLS ROYCE/BENTLEY - TWO |
| LAVATORIES ARE SHOWN ON THE SANITARY RISER FOR ROOM |
| #126 AND ONLY ONE IS SHOWN ON SHT. P1.3. CLARIFY. |
| 30) SHT.P1.3 SHOWS A 4"SANITARY RISER ON COLUMN LINE BB |
| BETWEEN COLS. #7 & #8 BUT IS NOT SHOWN ON THE SANITARY |
| RISER SHT. P2.1.. CLARIFY. |
| 31) SHT.P1.3 - SHOWS A SANITARY BRANCH FROM THE |
| BUILDING DRAIN GOING OVER TO STAIR #2 WITH A NOTE " 2" |
| SANITARY FROM ABOVE" BUT IT IS NOT SHOWN ON SHT. P2.1, |
| RISER #1(ROLLS ROYCE/BENTLEY0. CLARIFY. |
| 32) SHT. P1.6 - THE DISCHARGE FROM THE WASH BAYS SHALL |
| DISCHARGE THROUGH THE OIL SEPARATOR. 2014 FPC SEC. |
| 1003.4. |
| 33) SHT.P2.4 - WATER RISER #5 - HOT WATER IS REQUIRED |
| TO THE MOP SINK IN ROOM #156. 2014 FBC SEC.607.1. |
| 34) SHT.P0.3 - PROVIDE THE DIMENSIONS OF THE OIL |
| SEPARATOR.THE OIL SEPARATOR SHALL BE SIZED IN |
| ACCCORDANCE WITH THE 2014 FPC SECS. 1003.4.2, |
| 1003.4.2.1, 1003.4.2.2. |
| 35) SHT.P1.0 - THE DRINKING FOUNTAINS ARE SHOWN ON THE |
| FLOOR PLAN BUT ARE NOT SHOWN ON THE WATER RISER ON SHT. |
| P2.4 (RISER #5 RESTROOMS #154 & 155 ) . CLARIFY. |
| 36) SHT.P1.0A - DRINKING FOUNTAINS IN PASSAGE AREA #206 |
| ARE SHOWN ON THE FLOOR PLAN BUT NOT ON THE WATER RISER |
| ON SHT.P2.4. CLARIFY.SEE AREA BY COLS.15 & 0.2. |
| 37) SHT. P2.3 - HOT WATER IS REQUIRED TO THE MOP SINK |
| BY STORAGE ROOM #116. 2014 FPC SEC.607.1. |
| 38) SHT. P1.2 - THE PLAN VIEW FOR THE AREA NEAR STORAGE |
| ROOM #116 DOES NOT CORRELATE WITH SHT. A1.1. CLARIFY. |
| 39) SHT.P2.5 - THE MAXIMUM SQUARE FOOTAGE TO BE DRAINED |
| BY AN 8" HORIZONTAL DRAIN IS 9200 SQ. FT.PER 2014 FBC |
| TABLE 1106.3. RISER S-1 SHOWS AN 8" DRAIN DRAINING |
| 11,500 SQ. FT. |
| |
| PLUMBING PLAN REVIEW |