Plan Review Notes
Plan Review Notes For Permit 15120536
Permit Number 15120536
Review Stop P
Sequence Number 1
Notes
Date Text
2016-01-19 09:49:151) PROVIDE MATCH LINES FOR THE PLUMBING PLAN VIEW
 DRAWINGS. IT IS DIFFICULT TO FOLLOW THE CONTINUATION OF
 THE PLUMBING SYSTEM FROM ONE SHEET TO THE NEXT.WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) CLARIFY THE OCCUPANCY TYPE THAT YOU ARE USING TO
 CALCULATE THE REQUIRED PLUMBING FIXTURES FOR THE
 PORSCHE & BENTLEY AREAS.
 3) THE ARCHITECTURAL PLANS HAVE THE DIFFERENT AREAS
 LABELE "A - F" AND THE PLUMBING PLANS ARE LABELED BY
 THE AREA NAME ( PORSCHE-SOUTH, PORSCHE-NORTH, ROLLS
 ROYCE/BENTLEY ETC.). IT IS EXTREMELY DIFFICULT TO
 REVIEW THESE PLANS WITHOUT CORRELATING NAMING
 CONVENTIONS. PLEASE ATTEMPT TO CORRELATE THE
 IDENTIFICATION OF THESE PLANS IN A MANNER THAT MAKES IT
 EFFICIENT TO PERFORM A COMPREHENSIVE REVIEW.
 4) THE TRENCH DRAINS LOCATED IN THE DETAIL AREA #166
 SHALL DISCHARGE TO THE OIL INTERCEPTOR PER THE 2014
 FBC-PLUMBING SEC.1003.4.2.2.
 5) SHT. A1.1.1E - LOCKER ROOMS #125 & #126 SHOWS A
 HANDICAPPED ACCESSIBLE TOILET COMPARTMENT WITH A
 LAVATORY IN IT BUT NO WATER CLOSET. CLARIFY. 2014
 FBC-ACCESS. SEC.213.3.1 & 604.8.1.
 6) SHT. A1.1.1E - LOCKER RM. 3126 - SHOWS THE DOOR FOR
 THE ACCESSIBLE STALL SWINGING INTO THE CLEAR FLOOR
 SPACE FOR WHAT APPEARS TO BE AN ACCESSIBLE URINAL. THE
 DOOR CANNOT SWING INTO THE CLEAR FLOOR SPACE FOR THE
 FIXTURE PER 2014 FBC-ACCESS.SEC.603.2.3.
 7) SHT. A1.2.1 - THE BREAK ROOM SINK IN ROOM #209 SHALL
 COMPLY WITH 2014 FBC-ACCESS. SEC.212 & 606.
 8) SHT. A1.5.1 - TOILET ROOM # 500A - SHOW THE WIDTH OF
 THE TOILET ROOM ON DETAIL #2. THE MINIMUM WIDTH IS 85
 INCHES. 86 INCHES ALLOWS FOR TOLERANCE.
 9).SHOW THE INSIDE CLEAR DIMENSIONS (LXW) OF ALL SINGLE
 USER TOILET ROOMS. WPB AMEND. TO FBC SEC. 107.2.1.
 10) SHT. A2.0 - DETAILS #2 & #4 - IDENTIFY THE
 HANDICAPPED ACCESSIBLE URINAL IN BOTH RESTROOMS. COMPLY
 WITH 2014 FBC - ACCESS. SEC.605.
 11) SHT. A2.0 - SHOW THE FIXTURE CLEARANCE DIMENSION
 FROM THE CENTERLINE OF THE ACCESSIBLE WATER CLOSET TO
 THE SIDE WALL. COMPLY WITH 2014 FBC-ACCESS. SEC. 604.2.
 12) SHT.A2.0 - DETAIL #1 - THE DOORS TO RESTROOMS #213
 & 214 CANNOT SWING INTO THE CLEAR FLOOR SPACE FOR THE
 LAVATORIES. 2014 FBC-ACCESS. SEC.603.2.3. (SEE
 EXCEPTION #2).
 13) SHT. A2.0 - SHOW THE FIXTURE CLEARANCES OF THE
 URINALS ON SHT. A2.0, DETAIL #2 AND ALSO DETAIL #4.
 .COMPLY WITH 2014 FBC-PLUMBING, SEC.405.3.1.
 14) SHT. A2.1 - SHOW THE FIXTURE CLEARANCE FOR THE
 URINALS IN THE ENLARGED STAFF LOCKERS/RESTROOMS, DETAIL
 #2. COMPLY WITH 2014 FBC-PLUMBING SEC. 405.3.1.
 15) SHT. A2.0 - DETAIL #4 - THE DRINKING FOUNTAINS
 SHALL CCOMPLY WITH 2014 FBC-ACCESS. SEC.307.2 FOR
 PROTRUDING OBJECTS.
 16) SHT. A2.1 - DETAIL #2 - SHOW THE REQUIRED TURNING
 SPACE IN THE MEN'S & WOMEN'S RESTROOMS PER THE 2014
 FBC- ACCESS. SEC.304.3.1.
 17) SHT. A2.1 - DETAIL #1 - SHOW THE INSIDE CLEAR
 DIMENSION OF THE ACCESSIBLE STALL IN THE WWOMEN'S
 RESTROOM. MINIMUM WIDTH IS 85 INCHES. 86 INCHES ALLOWS
 FOR TOLERANCE. ALSO, SHOW THE FIXTURE CLEARANCE OF THE
 WATER CLOSET IN THE STALL FROM THE SIDE WALL TO THE
 CENTERLINE OF THE WATER CLOSET.
 18) SHT. A10.1 - THE URINAL SCREEN SHALL EXTEND NOT
 LESS THAN 60 INCHES ABOVE THE FINISH FLOOR.2014 FBC
 SEC. 1210.3.2.
 19) SHT. A10.1 - SHOW THE REQUIRED CLEAR FLOOR SPACE
 UNDER THE LAVATORY IN DETAIL #7. COMPLY WITH 2014
 FBC-ACCESS. SEC.305, 306.
 20) SHT.A10.3 - DETAILS #7 & #8 - THE HEIGHT OF THE
 WATER CLOSET IS SHOWN AS 15 INCHES ABOVE THE FINISH
 FLOOR. THE HEIGHT OF THE ACCESSIBLE WATER CLOSET SHALL
 BE BETWEEN 17" & 19 " ABOVE THE FINISH FLOOR. 2014 FBC-
 ACCESS. SEC.604.4.
 21) SHT. A10.7 - DETAIL #6 - THE URINAL LIP IS SHOWN AS
 1'-7" ABOVE THE FINISH FLOOR. IF THIS IS A HANDICAPPED
 URINAL, THE MAX. HEIGHT TO THE URINAL LIP SHALL BE 17
 INCHES. FBC-ACCESS. SEC. 605.2.
 22) SHT.A10.7 - DETAIL # 16 - THE URINAL LIP IS SHOWN
 AS 1'-7" ABOVE THE FINISH FLOOR. IF THIS IS A
 HANDICAPPED URINAL, THE MAX. HEIGHT TO THE URINAL LIP
 SHALL BE 17 INCHES. FBC-ACCESS. SEC. 605.2.
 23) SHT. P1.1 - IDENTIFY ALL THE EQUIPMENT & TANKS IN
 ROMM #171. WPB AMEND. TO FBC SEC.107.2.1.
 24) SUBMIT A PIPING RISER FOR THE COMPRESSED AIR
 SYSTEM.WPB AMEND. TO FBC SEC.107.2.1.
 25) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW. WPB
 AMEND. TO FBC SEC.107.2.1.
 26) CLEARLY SHOW THE DRAIN LINES FROM THE ELEVATOR
 SUMPS TO THE OIL WASTE SYSTEM ON THE PLUMBING RISER.WPB
 AMEND. TO FBC SEC.107.2.1.
 27) SHT.P2.2 - MEN'S & WOMEN'S TOILET ROOMS #154 & #155
 - THE CIRCUIT VENT SHALL BE LOCATED BETWEEN THE THE TWO
 MOST UPSTREAM FIXTURE DRAINS. AS DRAWN, THE VENT IS
 LOCATED DOWNSTREAM OF THE TWO MOST UPSTREAM WATER
 CLOSETS.2014 FPC SEC.914.2.
 28) SHT. P2.1 - SANITARY RISER #2 - TECH RESTROOMS -
 SIZE THE VENTS FOR THE URINALS.
 29) SHT. P2.1 - RISER #1 - ROLLS ROYCE/BENTLEY - TWO
 LAVATORIES ARE SHOWN ON THE SANITARY RISER FOR ROOM
 #126 AND ONLY ONE IS SHOWN ON SHT. P1.3. CLARIFY.
 30) SHT.P1.3 SHOWS A 4"SANITARY RISER ON COLUMN LINE BB
 BETWEEN COLS. #7 & #8 BUT IS NOT SHOWN ON THE SANITARY
 RISER SHT. P2.1.. CLARIFY.
 31) SHT.P1.3 - SHOWS A SANITARY BRANCH FROM THE
 BUILDING DRAIN GOING OVER TO STAIR #2 WITH A NOTE " 2"
 SANITARY FROM ABOVE" BUT IT IS NOT SHOWN ON SHT. P2.1,
 RISER #1(ROLLS ROYCE/BENTLEY0. CLARIFY.
 32) SHT. P1.6 - THE DISCHARGE FROM THE WASH BAYS SHALL
 DISCHARGE THROUGH THE OIL SEPARATOR. 2014 FPC SEC.
 1003.4.
 33) SHT.P2.4 - WATER RISER #5 - HOT WATER IS REQUIRED
 TO THE MOP SINK IN ROOM #156. 2014 FBC SEC.607.1.
 34) SHT.P0.3 - PROVIDE THE DIMENSIONS OF THE OIL
 SEPARATOR.THE OIL SEPARATOR SHALL BE SIZED IN
 ACCCORDANCE WITH THE 2014 FPC SECS. 1003.4.2,
 1003.4.2.1, 1003.4.2.2.
 35) SHT.P1.0 - THE DRINKING FOUNTAINS ARE SHOWN ON THE
 FLOOR PLAN BUT ARE NOT SHOWN ON THE WATER RISER ON SHT.
 P2.4 (RISER #5 RESTROOMS #154 & 155 ) . CLARIFY.
 36) SHT.P1.0A - DRINKING FOUNTAINS IN PASSAGE AREA #206
 ARE SHOWN ON THE FLOOR PLAN BUT NOT ON THE WATER RISER
 ON SHT.P2.4. CLARIFY.SEE AREA BY COLS.15 & 0.2.
 37) SHT. P2.3 - HOT WATER IS REQUIRED TO THE MOP SINK
 BY STORAGE ROOM #116. 2014 FPC SEC.607.1.
 38) SHT. P1.2 - THE PLAN VIEW FOR THE AREA NEAR STORAGE
 ROOM #116 DOES NOT CORRELATE WITH SHT. A1.1. CLARIFY.
 39) SHT.P2.5 - THE MAXIMUM SQUARE FOOTAGE TO BE DRAINED
 BY AN 8" HORIZONTAL DRAIN IS 9200 SQ. FT.PER 2014 FBC
 TABLE 1106.3. RISER S-1 SHOWS AN 8" DRAIN DRAINING
 11,500 SQ. FT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  