2015-12-30 14:32:43 | 1ST REVIEW: FBC 2014 MECHANICAL |
| PERMIT #15120536 |
| 12/30/15 |
| |
| 1) THE ENERGY CALCULATION FORM 506-2014 MUST BE |
| CERTIFIED WITH SIGNATURES OF THE LICENSED DESIGN |
| PROFESSIONALS OF THE PROPOSED PROJECT- SECTION C103.1.1 |
| FBC-14 ENERGY CONSERVATION. |
| 2) THE ASHRAE 90.1 MANDATORY COMPLIANCE CHECKLIST MUST |
| BE COMPLETED AND ATTACHED TO FORM 506-2014. |
| 3) ENERGY COMPLIANCE DATA FOR THE FOLLOWING SYSTEMS |
| SHOWN ON THE PLANS WAS NOT LISTED IN FORM 506-2014: |
| RTU'S 6, 7, 8, 9, & 10; AHU'S 6, 7, 8, 9, & 10; AND |
| MINI-SPLIT SYSTEMS MS- 1, 2, 4, & 5. |
| 4) RTU-3 IS LISTED AS 13 SEER IN THE AC SCHEDULE BUT |
| LISTED AS 12 EER IN FORM 506-2014- PLEASE SEE TABLE |
| C403.2.3(1) FBC-14 ENERGY CONSERVATION. |
| 5) THE AC LOAD CALCS INDICATE 4575 CFM'S OF OUTSIDE |
| VENTILATION AIR FOR AHU- 1&2, HOWEVER THOSE SYSTEMS ARE |
| NOT INCLUDED IN THE OUTDOOR AIR CALCULATIONS AND |
| SCHEDULE ON SHEET M0.2, AND THERE IS NO O/A DUCT SHOWN |
| ON THE PLANS FOR THOSE UNITS. |
| 6) THE AC LOAD CALCS INDICATE 522 CFM'S OF OUTSIDE |
| VENTILATION AIR FOR AHU-11, HOWEVER THE SYSTEM IS NOT |
| INCLUDED IN THE O/A CALCS OR SCHEDULE ON M0.2, AND |
| THERE IS NO O/A DUCT SHOWN ON THE PLAN FOR THE SYSTEM. |
| 7) PLEASE REMOVE RTU-5 FROM THE O/A SCHEDULE: IT IS NOT |
| IN THE EQUIPMENT SCHEDULE OR THE CALCS. |
| 8) HOW IS O/A BEING PROVIDED TO AHU'S 3, 4, 5, & 9. THE |
| PLAN DOES NOT INDICATE A MEANS OF SUPPLY. |
| 9) M0.2: THE O/A CALCULATION FOR THE PORSCHE SHOWROOM |
| (RTU-1) IS INCORRECT. THE MINIMAL O/A REQUIRED IS 822 |
| CFM'S. PLEASE REVIEW THE AC LOAD CALCS FOR THE SYSTEM. |
| 10) M1.0: PLEASE REVIEW SECTION 3006.2 FBC-14 BUILDING |
| (VENTING FOR ELEVATOR MACHINE ROOMS). CLARIFY IF THE |
| STORAGE ROOM BY THE ELEVATOR MEETS THE CRITERIA LISTED |
| IN THE CODE SECTION. PLEASE NOTE AN INDEPENDENT AC |
| SYSTEM MAY BE REQUIRED. |
| 11) M1.0A: THE E90 DIFFUSERS SHOWN AT ELEVATOR 2 AND |
| THE SEATING AREA ARE MISLABELED PER THE TERMINAL |
| SCHEDULE ON M0.1. |
| 12) M1.1: THE EXHAUST TERMINATION OUTLETS FOR EF-3, & 4 |
| ARE NOT SHOWN TO BE DISCHARGING TO THE EXTERIOR OF THE |
| BUILDING. PLEASE CLARIFY AND SEE SECTION 501.3.1 FOR |
| COMPLIANCE REQUIREMENTS. |
| 13) M1.2: THE EB150 RETURN GRILLS IN THE LOCKER ROOMS |
| ARE MISLABELED PER THE TERMINAL SCHEDULE ON M0.1. |
| 14) M1.5: CLARIFY HOW MAKE-UP AIR IS BEING PROVIDED FOR |
| GARAGE LEVEL 2 EXHAUST, AND PROVIDE A CALCULATION. |
| 15) PROVIDE A SEQUENCE OF OPERATION FOR THE DUCT SMOKE |
| DETECTORS, AND CLARIFY IF SYSTEMS IN THE SAME FIRE |
| AREAS OR FLOORS WILL BE LINKED TOGETHER FOR FAN |
| SHUTDOWN. IF THESE DETAILS ARE ON THE FIRE ALARM PLANS |
| PLEASE REFERENCE THE SHEET NUMBER ON THE MECHANICAL |
| PLANS. |
| 16) PROVIDE SUPPORT AND HANGING DETAILS FOR |
| INSTALLATION OF THE AHU'S AND VAV BOXES. |
| 17) INDICATE HOW ACCESS FOR SERVICING AND REPLACEMENT |
| OF THE AHU'S AND VAV BOXES WILL BE PROVIDED- SECTION |
| 306.1 FBC-14 MECHANICAL. |
| 18) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE C0 AND |
| N02 DETECTORS WITH REVIEW AND APPROVAL SIGNATURES FROM |
| THE ENGINEER OF RECORD. |
| 19) SUBMIT FL. PRODUCT APPROVALS AND/OR MIAMI-DADE |
| NOA'S FOR THE EXHAUST AND AIR INTAKE LOUVERS, THE ROOF |
| STANDS, AND THE RTU CURBS, AND THE ROOF FAN CURBS. ALL |
| DOCUMENTS SHALL BEAR REVIEW AND APPROVAL SIGNATURES BY |
| THE EOR. |
| 20) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL |
| PLANS AND DETAILS FOR THE AHU'S AND THE MINI-SPLITS. |
| PLEASE SHOW THE PIPING RUNS AND DISCHARGE LOCATIONS ON |
| THE PLANS. |
| 21) SITE SPECIFIC ENEGINEERING IS REQUIRED FOR TIE-DOWN |
| OF ALL ROOF TOP MECHANICAL EQUIPMENT- SECTION 301.15 |
| FBC-14 MECHANICAL. THE DETAILS ON SHEET M5.0 ARE |
| INCOMPLETE AND REQUIRE SUBMITTALS FOR CURBS AND STANDS |
| THAT HAVE BEEN REVIEWED AND APPROVED BY THE ENGINEER OF |
| RECORD. THE ENGINEER OF RECORD SHALL PROVIDE THE NOA |
| NUMBERS FOR THE COMPONENTS ON THE BOTH THE STRUCTURAL |
| AND MECHANICAL PLANS. |
| |