2016-02-08 14:30:53INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. SHEET E0.1- PLEASE UPDATE GENERAL NOTE TO INDICATE
 AND REFLECT THE CURRENT FBC 2014 5TH EDITION AS THE
 CODE IN EFFECT AT THE TIME OF THIS REVIEW.
 2. SHEET ES1.1- PLEASE ADD A GENERAL NOTE TO SHEET TO
 INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE
 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND
 THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE
 LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL
 SUFFICE
 3. SHEET ES1.1- PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS
 FOR ALL SITE LIGHTING AND ASSOCIATED EQUIPMENT,
 GENERATOR, ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT
 LIMITED TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE AND
 DATA, SIGNAGE, WIRELESS SYSTEMS, CAR CHARGING STATIONS,
 ETC. A NOTE WILL SUFFICE.
 4. SHEET E1.0- PLEASE LABEL RECEPTACLE ON CIRCUIT L32
 TO BE GFCI PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF
 SINK ALL TO BE GFCI.
 5. SHEET E1.0- NOTE INDICATING THE CLASSIFICATION OF
 AREAS AS NOTED IN NEC 511.3 IS TOO VAGUE AS TO THE
 AREA, PER ENGINEER OF RECORD (EOR) THAT ARE TO BE
 CLASSIFIED. PLEASE CLARIFY THE DESIGN INTENT AND LABEL
 THE FLOOR PLANS ACCORDINGLY.
 6. SHEET E1.1- THE RECEPTACLE OUTLETS IN THE BREAK ROOM
 THAT ARE WITHIN 6FT OF THE SINK MUST BE LABELED GFCI
 NEC 210.8B5
 7. SHEET E1.1- THE RECEPTACLES OUTLETS SERVING THE
 SERVICE BAY REPAIR AREAS MUST ALL BE GFCI PROTECTED PER
 NEC 511.12, ROOM 169.
 8. SHEET E1.2- THE RECEPTACLE OUTLETS IN THE BREAK ROOM
 THAT ARE WITHIN 6FT OF THE SINK MUST BE LABELED GFCI
 NEC 210.8B5
 9. SHEET 1.3- LABEL CIRCUIT L7-26 TO DRINKING FOUNTAIN
 GFCI PROTECTED PER NEC 422.52
 10. SHEET 1.3- THE RECEPTACLES OUTLETS SERVING THE
 SERVICE BAY REPAIR AREAS MUST ALL BE GFCI PROTECTED PER
 NEC 511.12
 11. SHEET 1.4- THE RECEPTACLES OUTLETS SERVING THE
 SERVICE BAY REPAIR AREAS MUST ALL BE GFCI PROTECTED PER
 NEC 511.12
 12. SHEET 1.4- THE FIRE PUMP NOTES INDICATE ?DRAWINGS
 TO BE PROVIDED BY OTHERS? A COMPLETE REVIEW COULD NOT
 BE PERFORMED AT THIS TIME.
 13. SHEET 3.1- PLEASE NOTE THAT ALL MAIN DISCONNECTS
 MUST BE GROUPED AT THE SAME LOCATION PER NEC 230.72A.
 ALSO NEC 230.2 REQUIRES THAT BUILDINGS BE SUPPLIED BY
 ONLY ONE SERVICE UNLESS PERMITTED BY NEC 230.2A THROUGH
 230.2D. THE ARRANGEMENTS OF THE ELECTRICAL SERVICE
 SHOWN PER PHASING INTENT MUST BE APPROVED BY SPECIAL
 PERMISSION OF THE AHJ. PROVIDE REQUEST IN WRITING WHICH
 IS SUBJECT TO APPROVAL.
 14. SHEET 3.2- RISER DIAGRAM AT THIS TIME WILL NEED TO
 BE REVISITED PENDING APPROVAL AS NOTED IN COMMENT #13.
 SEE ABOVE.
 15. SHEETS 4.1 THROUGH 4.4- PANEL SCHEDULES AT THIS
 TIME WILL NEED TO BE REVISITED PENDING APPROVAL AS
 NOTED IN COMMENT #13. SEE ABOVE.
 16. SHEET 5.3- ELECTRICAL ROOMS MUST COMPLY WITH NEC
 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF
 THE WORKING SPACE. SHOW TWO MEANS OF EXIT FOR ROOM 170.
 ALSO NEC 110.26C3 REQUIRES PERSONNEL DOORS TO BE
 EQUIPPED WITH PANIC HARDWARE AND OPEN IN THE DIRECTION
 OF EGRESS. A NOTE WILL SUFFICE.
 17. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  