2016-02-08 14:30:53 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| |
| 1. SHEET E0.1- PLEASE UPDATE GENERAL NOTE TO INDICATE |
| AND REFLECT THE CURRENT FBC 2014 5TH EDITION AS THE |
| CODE IN EFFECT AT THE TIME OF THIS REVIEW. |
| 2. SHEET ES1.1- PLEASE ADD A GENERAL NOTE TO SHEET TO |
| INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE |
| 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND |
| THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE |
| LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL |
| SUFFICE |
| 3. SHEET ES1.1- PROVIDE A BLOCK NOTE INDICATING THE |
| REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS |
| FOR ALL SITE LIGHTING AND ASSOCIATED EQUIPMENT, |
| GENERATOR, ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT |
| LIMITED TO FIRE ALARM, ACCESS CONTROLS, CCTV, PHONE AND |
| DATA, SIGNAGE, WIRELESS SYSTEMS, CAR CHARGING STATIONS, |
| ETC. A NOTE WILL SUFFICE. |
| 4. SHEET E1.0- PLEASE LABEL RECEPTACLE ON CIRCUIT L32 |
| TO BE GFCI PROTECTED PER NEC 210.8B5- IF WITHIN 6FT OF |
| SINK ALL TO BE GFCI. |
| 5. SHEET E1.0- NOTE INDICATING THE CLASSIFICATION OF |
| AREAS AS NOTED IN NEC 511.3 IS TOO VAGUE AS TO THE |
| AREA, PER ENGINEER OF RECORD (EOR) THAT ARE TO BE |
| CLASSIFIED. PLEASE CLARIFY THE DESIGN INTENT AND LABEL |
| THE FLOOR PLANS ACCORDINGLY. |
| 6. SHEET E1.1- THE RECEPTACLE OUTLETS IN THE BREAK ROOM |
| THAT ARE WITHIN 6FT OF THE SINK MUST BE LABELED GFCI |
| NEC 210.8B5 |
| 7. SHEET E1.1- THE RECEPTACLES OUTLETS SERVING THE |
| SERVICE BAY REPAIR AREAS MUST ALL BE GFCI PROTECTED PER |
| NEC 511.12, ROOM 169. |
| 8. SHEET E1.2- THE RECEPTACLE OUTLETS IN THE BREAK ROOM |
| THAT ARE WITHIN 6FT OF THE SINK MUST BE LABELED GFCI |
| NEC 210.8B5 |
| 9. SHEET 1.3- LABEL CIRCUIT L7-26 TO DRINKING FOUNTAIN |
| GFCI PROTECTED PER NEC 422.52 |
| 10. SHEET 1.3- THE RECEPTACLES OUTLETS SERVING THE |
| SERVICE BAY REPAIR AREAS MUST ALL BE GFCI PROTECTED PER |
| NEC 511.12 |
| 11. SHEET 1.4- THE RECEPTACLES OUTLETS SERVING THE |
| SERVICE BAY REPAIR AREAS MUST ALL BE GFCI PROTECTED PER |
| NEC 511.12 |
| 12. SHEET 1.4- THE FIRE PUMP NOTES INDICATE ?DRAWINGS |
| TO BE PROVIDED BY OTHERS? A COMPLETE REVIEW COULD NOT |
| BE PERFORMED AT THIS TIME. |
| 13. SHEET 3.1- PLEASE NOTE THAT ALL MAIN DISCONNECTS |
| MUST BE GROUPED AT THE SAME LOCATION PER NEC 230.72A. |
| ALSO NEC 230.2 REQUIRES THAT BUILDINGS BE SUPPLIED BY |
| ONLY ONE SERVICE UNLESS PERMITTED BY NEC 230.2A THROUGH |
| 230.2D. THE ARRANGEMENTS OF THE ELECTRICAL SERVICE |
| SHOWN PER PHASING INTENT MUST BE APPROVED BY SPECIAL |
| PERMISSION OF THE AHJ. PROVIDE REQUEST IN WRITING WHICH |
| IS SUBJECT TO APPROVAL. |
| 14. SHEET 3.2- RISER DIAGRAM AT THIS TIME WILL NEED TO |
| BE REVISITED PENDING APPROVAL AS NOTED IN COMMENT #13. |
| SEE ABOVE. |
| 15. SHEETS 4.1 THROUGH 4.4- PANEL SCHEDULES AT THIS |
| TIME WILL NEED TO BE REVISITED PENDING APPROVAL AS |
| NOTED IN COMMENT #13. SEE ABOVE. |
| 16. SHEET 5.3- ELECTRICAL ROOMS MUST COMPLY WITH NEC |
| 110.26C2, THERE SHALL BE ONE ENTRANCE AT EACH END OF |
| THE WORKING SPACE. SHOW TWO MEANS OF EXIT FOR ROOM 170. |
| ALSO NEC 110.26C3 REQUIRES PERSONNEL DOORS TO BE |
| EQUIPPED WITH PANIC HARDWARE AND OPEN IN THE DIRECTION |
| OF EGRESS. A NOTE WILL SUFFICE. |
| 17. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| REGARDING THIS PROJECT. |
| |
| |