2016-01-22 07:35:33 | 1ST REVIEW: FBC 2014 MECHANICAL |
| PERMIT #15120534 |
| 1/22/16 |
| |
| 1) THE AC SYSTEM SIZING CALCULATION WAS NOT PERFORMED |
| USING AN APPROVED CALCULATION METHODOLOGY AS REQUIRED |
| PER SECTION R4-03.6 FBC-14 ENERGY CONSERVATION. THE |
| SOFTWARE PROGRAM FROM HVAC COMPUTER SYSTEMS LTD. DOES |
| NOT HAVE ACCA APRROVAL OR ANY OTHER AGENCY APPROVAL. |
| 2) ENERGY COMPLIANCE FORM R405-2014: IT APPEARS THAT |
| MR. HUMBERTO DIAZ, WHO WAS THE PREPARER OF THE |
| DOCUMENT, HAS ALSIO PRINTED THE NAMES OF THE OWNERS ON |
| THE LINE WHERE THE OWNERS HAVE TO SIGN. PLEASE PROVIDE |
| AN ORIGINAL SIGNATURE FROM THE OWNERS OR THE DOCUMENT. |
| 3) ENERGY FORM R405-2014: THE DATA LISTED FOR THE DOORS |
| ON THE DOCUMENT DOES NOT MATCH THE PLAN WHICH SHOWS |
| ONLY TWO SOLID DOORS- ONE ON THE NORTH SIDE AND ONE ON |
| THE WEST SIDE. THE REMAINDER OF THE DOORS ARE SLIDING |
| GLASS TYPES- PLEASE CORRECT. |
| 4) SHEET M.1: SUFFICIENT SPACE MUST BE [PROVIDED FPOR |
| THE AIR HANDLER IN THE CLOSET. PLEASE REFER TO |
| M1305.1.1 FURNACES AND AIR HANDLERS FBC-14 RESIDENTIAL |
| AND SHOW COMPLIANCE ON THE PLAN: |
| FURNACES AND AIR HANDLERS WITHIN COMPARTMENTS OR |
| ALCOVES SHALL HAVE A MINIMUM WORKING SPACE CLEARANCE OF |
| 3 INCHES (76 MM) ALONG THE SIDES, BACK AND TOP WITH A |
| TOTAL WIDTH OF THE ENCLOSING SPACE BEING AT LEAST 12 |
| INCHES (305 MM) WIDER THAN THE FURNACE OR AIR HANDLER. |
| FURNACES HAVING A FIREBOX OPEN TO THE ATMOSPHERE SHALL |
| HAVE AT LEAST A 6-INCH (152 MM) WORKING SPACE ALONG THE |
| FRONT COMBUSTION CHAMBER SIDE. COMBUSTION AIR OPENINGS |
| AT THE REAR OR SIDE OF THE COMPARTMENT SHALL COMPLY |
| WITH THE REQUIREMENTS OF CHAPTER 17. |
| 5) M.1: KEY NOTES ARE PROVIDED HOWEVER THEIR RELATIVE |
| LOCATIONS ON THE PLAN ARE NOT SHOWN. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |