2016-01-06 15:44:14THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. NEC 300.5(B). YOUR NOTES INDICATE THHN CONDUCTOR
 INSULATION UON. PLEASE BE AWARE THAT THE INTERIOR OF
 ANY UNDERGROUND RACEWAY IS CONSIDERED A WET LOCATION
 THUS THWN IS REQUIRED.
 2. NEC 406.9(B), RECEPTACLES OUTDOORS OR EXPOSED TO THE
 WEATHER SHALL BE LISTED WEATHER-RESISTANT ?WR?.
 3. REVISE NOTE 9 TO REFLECT THE CURRENT/APPLICABLE
 CODE. NEC 2011 AND ARTICLE 406.12 ADDRESSES THE
 TAMPER-RESISTANT RECEPTACLES.
 4. THE WORD ?ROMEX? AS USED IN YOUR NOTE IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE; REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 5. NEC 422.15 CENTRAL VACUUM OUTLETS. ALL CENTRAL
 VACUUM OUTLET ASSEMBLIES SHALL COMPLY AS INDICATED
 HEREIN.
 6. NEC 210.12, ARC-FAULT CIRCUIT PROTECTION SHALL BE
 INSTALLED AS INDICATED.
 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 8. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
 9. NEC 410.110 & FBC-E C402.4.8 RECESSED LIGHTING.
 RECESSED LIGHTING INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE IC RATED AND BE SEALED TO LIMIT AIR
 LEAKAGE BETWEEN CONDITIONED & UNCONDITIONED SPACES.
 10. NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 11. NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT.
 OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. THIS
 INCLUDES THE WALL ADJACENT TO THE REAR DOOR.
 12. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 13. NEC 210.8 GROUND FAULT CIRCUIT-INTERRUPTER
 PROTECTION. GFI REQUIRED FOR THE OUTLET ADJACENT TO THE
 SINK IN THE LAUNDRY ROOM & THE OUTLET IN THE MASTER
 BEDROOM IF LESS THAN 6FT. FROM SINK.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  