2016-01-06 15:44:14 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| 1. NEC 300.5(B). YOUR NOTES INDICATE THHN CONDUCTOR |
| INSULATION UON. PLEASE BE AWARE THAT THE INTERIOR OF |
| ANY UNDERGROUND RACEWAY IS CONSIDERED A WET LOCATION |
| THUS THWN IS REQUIRED. |
| 2. NEC 406.9(B), RECEPTACLES OUTDOORS OR EXPOSED TO THE |
| WEATHER SHALL BE LISTED WEATHER-RESISTANT ?WR?. |
| 3. REVISE NOTE 9 TO REFLECT THE CURRENT/APPLICABLE |
| CODE. NEC 2011 AND ARTICLE 406.12 ADDRESSES THE |
| TAMPER-RESISTANT RECEPTACLES. |
| 4. THE WORD ?ROMEX? AS USED IN YOUR NOTE IS TO IDENTIFY |
| A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE |
| OF CABLE; REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?. |
| 5. NEC 422.15 CENTRAL VACUUM OUTLETS. ALL CENTRAL |
| VACUUM OUTLET ASSEMBLIES SHALL COMPLY AS INDICATED |
| HEREIN. |
| 6. NEC 210.12, ARC-FAULT CIRCUIT PROTECTION SHALL BE |
| INSTALLED AS INDICATED. |
| 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT |
| LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE |
| REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF |
| 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE. |
| 8. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE |
| SUPPORT OF CEILING FANS SHALL BE MARKED BY THE |
| MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE |
| THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT |
| PADDLE FANS HEAVIER THAN 70 LBS. |
| 9. NEC 410.110 & FBC-E C402.4.8 RECESSED LIGHTING. |
| RECESSED LIGHTING INSTALLED IN THE BUILDING THERMAL |
| ENVELOPE SHALL BE IC RATED AND BE SEALED TO LIMIT AIR |
| LEAKAGE BETWEEN CONDITIONED & UNCONDITIONED SPACES. |
| 10. NEC 250.94 BONDING FOR OTHER SYSTEMS. THE |
| INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE |
| INSTALLED. |
| 11. NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT. |
| OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. THIS |
| INCLUDES THE WALL ADJACENT TO THE REAR DOOR. |
| 12. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT |
| LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH |
| PENINSULAR COUNTERTOP. |
| 13. NEC 210.8 GROUND FAULT CIRCUIT-INTERRUPTER |
| PROTECTION. GFI REQUIRED FOR THE OUTLET ADJACENT TO THE |
| SINK IN THE LAUNDRY ROOM & THE OUTLET IN THE MASTER |
| BEDROOM IF LESS THAN 6FT. FROM SINK. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |