Date |
Text |
2016-01-12 12:25:28 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| |
| PLANS INDICATE NEW ROOFING AND WINDOWS. DISCUSSION WITH |
| CONTRACTOR INDICATES ROOFING IS BY EXISTING PERMIT |
| 15110990 AND WINDOWS WILL BE BY SEPARATE PERMIT UNDER |
| SEPARATE CONTRACT AND ACCORDINGLY NOT PART OF THE SCOPE |
| OF THIS PERMIT. PLEASE VERIFY AND MODIFY THE PLAN TO SO |
| INDICATE. OTHERWISE, PROVIDE PRODUCT APPROVALS REVIEWED |
| BY THE DESIGNER OF RECORD. |
| |
| FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| PROVIDE STRUCTURAL AND WALL FINISH DETAILS FOR THE NEW |
| INFILL WALL AT OUTDOOR SHOWER AREA ON SHEET A100.1. |
| PROVIDE STRUCTURAL AND BUCK DETAILS FOR NEW WINDOW |
| OPENINGS AND AS INDICATED ABOVE CLARIFY WHOM SHALL BE |
| RESPONSIBLE FOR WINDOW PRODUCTS. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| INDICATE SMOKE/CARBON MONOXIDE INFORMATION. |
| |
| FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO |
| FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| |
| FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 |
| FEET OF EACH SLEEPING ROOM. |
| |