2016-01-12 12:25:281ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 PLANS INDICATE NEW ROOFING AND WINDOWS. DISCUSSION WITH
 CONTRACTOR INDICATES ROOFING IS BY EXISTING PERMIT
 15110990 AND WINDOWS WILL BE BY SEPARATE PERMIT UNDER
 SEPARATE CONTRACT AND ACCORDINGLY NOT PART OF THE SCOPE
 OF THIS PERMIT. PLEASE VERIFY AND MODIFY THE PLAN TO SO
 INDICATE. OTHERWISE, PROVIDE PRODUCT APPROVALS REVIEWED
 BY THE DESIGNER OF RECORD.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PROVIDE STRUCTURAL AND WALL FINISH DETAILS FOR THE NEW
 INFILL WALL AT OUTDOOR SHOWER AREA ON SHEET A100.1.
 PROVIDE STRUCTURAL AND BUCK DETAILS FOR NEW WINDOW
 OPENINGS AND AS INDICATED ABOVE CLARIFY WHOM SHALL BE
 RESPONSIBLE FOR WINDOW PRODUCTS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 INDICATE SMOKE/CARBON MONOXIDE INFORMATION.
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710