Plan Review Notes For Permit 15120482 |
Permit Number |
15120482 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-05 08:46:13 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL | | | | 1) THE CODE REFERENCE OF NEC 2008 ON SHEET E01 IS | | INCORRECT, THE CORRECT CODE REFERENCE IS FBC 2014 5TH | | ED. RESIDENTIAL AND IT CONTAINS ELECTRICAL REQUIREMENTS | | IN THE ELECTRICAL SECTION. PLEASE REVISE. | | | | 2) THE PANEL SCHEDULE NOR CIRCUTING ON THE PLAN | | INDICATE PROVISIONS FOR TWO KITCHEN/DINING CIRCUITS. | | FBCRE3703.2 KITCHEN AND DINING AREA RECEPTACLES. A | | MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL BE | | PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE OUTLETS | | LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA, DINING | | AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN | | COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF | | TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF | | WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER | | RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY, | | BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS | | FOR REFRIGERATION APPLIANCES. | | | | 3) THE PANEL SCHEDULE AND AIR CONDITIONING EQUIPMENT | | ARE NOT CONSISTENT IN TERMS OF THE NUMBER OF SYSTEMS. | | | | 4) PLEASE INDICATE THE LOCATION OF THE ELECTRICAL | | SERVICE EQUIPMENT ON THE PLAN. | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|