Plan Review Notes For Permit 15120430 |
Permit Number |
15120430 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-27 10:46:43 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | MEANS. NEC 110.16, 110.22 | | PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE | | RECEPTACLES. NEC 210.8 | | PROVIDE A INTERSYSTEM BONDING BAR AT THE ELECTRICAL | | SERVICE. NEC 250 .94 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | |
|