2015-12-30 13:42:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY, FBC
 107, FBC 705.3, 705.8.
  
 2. CVR 1, TOP CENTER STATES THAT THIS IS A COMMERCIAL
 REMODEL, PLEASE REVISE, FBC 107.
  
 3. FOR SHEETS WHICH ARE REVISED, INCLUDE THE FOLLOWING
 INFORMATION IN THE TITLE BLOCK AS REQUIRED BY
 61G1-16.004:
  
 FIRM LICENSE NUMBER
 THE PRINTED NAME AND THE LICENSE LUMBER OF THE PERSON
 SEALING THE DOCUMENT
  
 PLEASE INCORPORATE REQUIRED INFORMATION INTO THE TITLE
 BLOCK OF FUTURE SUBMITTALS.
  
 4. PROVIDE A SITE PLAN WHICH SHOWS THE FOLLOWING:
  
 LOCATION OF ASSUMED PROPERTY LINE BETTWEEN THE EXISTING
 BUILDING(S) AND THE PROPOSED NEW BUILDING, FBC 705.3
 UNLESS USING THE EXCEPTION.
  
 BUILDING TYPE OF THE EXISTING BUILDING(S)
 DISTANCE OF EXISTING BUILDING(S) TO THE ASSUMED
 PROPERTY LINE
 COMPLIANCE WITH FBC 602, 705.8
  
 DISTANCE OF PROPOSED NEW CAR WASH BUILDING TO THE
 ASSUMED PROPERTY LINE AND ACTUAL PROPERTY LINES
 COMPLIANCE WITH FBC 602, 705.8
  
 IF USING THE EXCEPTION, SHOW COMPLIANCE WITH FBC TABLE
 503.
  
 5. CVR 1, BUILDING CODE DATA, USE IS MIXED USE, BUT
 ONLY ONE OCCUPANCY DECLARED (B), PLEASE CLARIFY, FBC
 107, CHAPTER 3.
  
 6. CVR 1, CONSTRUCTION TYPE DECLARED IS 1B. EITHER
 REVISE BUILDING TYPE OR SHOW COMPLIANCE WITH FBC TABLE
 601 (2 HOUR EXTERIOR BEARING WALL, 1 HOUR ROOF). IF THE
 BUILDING TYPE REMAINS 1B, PROVIDE INFORMATION FOR THE
 EIFS SYSTEM TO DEMONSTRATE THAT IT IS NON COMBUSTIBLE
 OR INCOPORATE THE APPLICABLE EXCEPTION INTO THE PLAN.
  
 7. CVR 1, OCCUPANT LOAD CALCULATION MAKES REFERENCE TO
 FBC 2010, PLEASE REVISE TO FBC 2014 (5TH EDITION) AS
 GOVERNING CODE CHANGED ON JUNE 30, 2015, FS553, FBC
 107.
  
 8. PROVIDE TWO SETS OF ALL PRODUCT APPROVALS, FBC 107.
 THEY ARE REQUIRED FOR PLAN REVIEW AND FOR INSPECTIONS.
 AS THE PRODUCT APPROVAL NUMBERS HAVE BEEN INCORPORATED
 INTO THE PLAN,
  
 9. THE STO PRODUCT SPECIFIED ON A1.0 APPEARS TO INCLUDE
 A TYPO; 15-1226.03 IS NOT A VALID NOA NUMBER.
  
 10. PROVIDE THE GEOTECHNICAL REPORT FOR PROPOSED SITE,
 REVIEWED BY DESIGNER OF RECORD, FBC 1803.2.
  
 11. REVISE PLAN TO INCLUDE SCUPPER AND OVERFLOW SIZING
 CALCULATIONS, FBC 1503.
  
  