2015-12-08 19:06:39 | RE-ROOF BUILDING REVIEW COMMENTS. |
| CODE: FBC-5TH EDITION (2014). |
| |
| 1- ACCORDING TO SEC. 1609.4 OF FBC-BUILDING, 5TH |
| EDITION THIS BUILDING IS LOCATED IN EXPOSURE "D" NOT |
| "C". ENGINEER DOING THE RAS 117 CALCULATIONS TO REVISE |
| CALCULATIONS AS REQUIRED.. NOTE: NEED TO SELECT ANOTHER |
| FLAT ROOF ASSEMBLY THAT MEETS THE CALCULATED REVISED |
| DESIGN PRESSURES. |
| |
| 2- THE BUILDING HEIGHT OF THIS BUILDING IS 110'. |
| PROVIDE SIGNED AND SEALED DETAILS AND SPECIFICATIONS |
| FOR THE ATTACHMENT OF THE COPING CAPS AND DRIP EDGE |
| SHOWING COMPLIANCE WITH THE WIND LOADS OF SEC. 1609 OF |
| FBC-BUILDING, 5TH EDITION. |
| |
| 3- SCOPE OF WORK SUBMITTED INCLUDES MECHANICAL UNITS |
| STANDS, MECHANICAL SHROUDS, CONSTRUCTION OF KNEE WALL, |
| REPLACE DOOR. THIS SCOPE OF WORK TO BE DONE UNDER |
| SEPARATE PERMITS. PROVIDE COMPLETE DETAILS/ |
| SPECIFICATIONS AND PRODUCT APPROVALS UNDER SEPARATE |
| PERMITS. NOTE: THIS SCOPE OF WORK CAN NOT BE DONE BY |
| THE ROOFING CONTRACTOR UNLESS THE ROOFING CONTRACTOR |
| POSSES A LICENSE TO PERFORM SUCH SCOPE OF WORK. SEC. |
| 489.113 FLORIDA STATUTES. |
| |