2015-12-09 06:07:44 | 1) THE OIL SEPARATOR DOES NOT CCOMPLY WITH THE 2014 |
| FBC-PLUMBING, SECS. 1003.4.1, 1003.4.2.1., 1003.4.2.2. |
| - THE OIL SEPARATOR SHALL HAVE A DEPTH OF NOT LESS THAN |
| 2 FT. BELOW THE INVERT OF THE DISCHARGE DRAIN.THE |
| OUTLET OPENING OF THE SEPARATOR SHALL HAVE NOT LESS |
| THAN AN 18 INCH WATER SEAL. |
| 2) THE OIL SEPARATORR SHALL HAVE A CAPACITY OF NOT LESS |
| THAN 6 CUBIC FEET FOR THE FIRST 100 SQUARE FEET OF AREA |
| TO BE DRAINED, PLUS 1 CUBIC FOOT FOR EACH ADDITIONAL |
| 100 SQUARE FEET OF AREA TO BE DRAINED INTO THE |
| SEPARATOR. |
| 3) SUBMIT THE TOTAL SQUARE FOOT AREA THAT IS GOING TO |
| BE DRAINED BY THE TRENCH DRAIN. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 4) SUBMIT FACTORY SIZING CALCULATIONS FOR THE OIL |
| SEPARATOR DONE BY SCHIER. CONTACT LEE SCHNEEWEISS AT |
| 1-800- 538-4792. |
| 5) THE DETAIL OF THE OS-25 WITH RISER SHOWS A 3 INCH |
| PIPE SIZE BUT THE SPECIFICATIONS LISTED AT THE BOTTOM |
| OF THE PAGE NOTES A 4 INCH INLET & OUTLET. CLARIFY. |
| 6) A SAMPLING PORT IS REQUIRED ON THE OUTLET OF THE |
| SEPARATOR. WPB AMEND. TO FBC SEC. 107.2.1. I WOULD |
| SUGGEST SPEAKING TO THE SCHIER REPRESENTATIVE REGARDING |
| THIS ITEM. |
| 7) SHOW THE REQUIRED CELANOUTS ON THE INTERCEPTOR. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 8) SHOW THE SIZE OF THE PIPE ENTERING AND LEAVING THE |
| INTERCEPTOR ON THE PLAN VIEW DRAWING. |
| 9) SUBMIT 2 COPIES OF INSTALLATION MANUAL FROM SCHIER |
| FOR THE PROPERLY SIZED UNIT. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| |