2015-12-07 16:01:17 | 1ST REVIEW 2014 MECHANICAL |
| PERMIT #15120216 |
| 12/7/15 |
| |
| 1) THERE IS CURRENTLY A PERMIT APPLICATION AND PLANS |
| SUBMITTED FOR A CHANGE OF OCCUPANCY AT THIS LOCATION |
| (428 AVON RD- PERMIT #15100233). I HAVE FAILED THE |
| SUBMITTED PLAN AND HAVE WRITTEN COMMENTS REQUESTING |
| ENERGY CALCULATIONS AND VENTILATION CALCULATIONS, |
| HOWEVER NO AC PLANS WERE SUBMITTED AT THAT TIME. |
| CONCERNING THIS NEW SUBMITTAL, WHICH HAS BEEN PROCESSED |
| AS A REVISION TO AN AC CHANGEOUT PERMIT ISSUED AT THE |
| SAME LOCATION (PERMIT #15100285), PLEASE REVIEW THE |
| FOLLOWING COMMENTS: |
| A) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH |
| SECTION C101.4.5 FBC-14 ENERGY CONSERVATION. |
| B) PROVIDE THE CFM QUANITIES AT EACH SUPPLY DIFFUSER. |
| C) PROVIDE THE SIZE OF THE RETURN AIR PLENUM, AND |
| INDICATE THE TYPE OF DUCTWORK TO BE INSTALLED- SECTION |
| 603 |
| D) PROVIDE DUCT HANGING AND CONNECTION DETAILS- SECTION |
| 603 |
| E) IDENTIFY ALL ROOMS AND SPACES ON THE PLANS AND |
| PROVIDE RETURN AIR WHERE REQUIRED- SEE SECTION 601.5. |
| F) PROVIDE AIR HANDLER INSTALLATION DETAILS. |
| G) PROVIDE AN AIR DEVICE SCHEDULE. |
| H) PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR |
| SYSTEM AS REQUIRED BY SECTION 606.2.1. |
| I) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR |
| INSTALLING THE EXTERIOR CONDENSER- SECTION 301.15. |
| PLEASE NOTE THE SUBMITTAL FOR THE ALUMSTAND HAS |
| ILLEGIBLE PRINT THAT IS TOO SMALL TO READ AND SCAN INTO |
| THE BUILDING DEPARTMENT RECORDS. |
| J) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL |
| PLANS- SECTION 307. |
| 2) PLEASE NOTE THAT AN ELECTRICAL PLAN AND SUB-PERMIT |
| WILL BE REQUIRED. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |