2015-12-07 16:01:171ST REVIEW 2014 MECHANICAL
 PERMIT #15120216
 12/7/15
  
 1) THERE IS CURRENTLY A PERMIT APPLICATION AND PLANS
 SUBMITTED FOR A CHANGE OF OCCUPANCY AT THIS LOCATION
 (428 AVON RD- PERMIT #15100233). I HAVE FAILED THE
 SUBMITTED PLAN AND HAVE WRITTEN COMMENTS REQUESTING
 ENERGY CALCULATIONS AND VENTILATION CALCULATIONS,
 HOWEVER NO AC PLANS WERE SUBMITTED AT THAT TIME.
 CONCERNING THIS NEW SUBMITTAL, WHICH HAS BEEN PROCESSED
 AS A REVISION TO AN AC CHANGEOUT PERMIT ISSUED AT THE
 SAME LOCATION (PERMIT #15100285), PLEASE REVIEW THE
 FOLLOWING COMMENTS:
 A) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH
 SECTION C101.4.5 FBC-14 ENERGY CONSERVATION.
 B) PROVIDE THE CFM QUANITIES AT EACH SUPPLY DIFFUSER.
 C) PROVIDE THE SIZE OF THE RETURN AIR PLENUM, AND
 INDICATE THE TYPE OF DUCTWORK TO BE INSTALLED- SECTION
 603
 D) PROVIDE DUCT HANGING AND CONNECTION DETAILS- SECTION
 603
 E) IDENTIFY ALL ROOMS AND SPACES ON THE PLANS AND
 PROVIDE RETURN AIR WHERE REQUIRED- SEE SECTION 601.5.
 F) PROVIDE AIR HANDLER INSTALLATION DETAILS.
 G) PROVIDE AN AIR DEVICE SCHEDULE.
 H) PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR
 SYSTEM AS REQUIRED BY SECTION 606.2.1.
 I) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR
 INSTALLING THE EXTERIOR CONDENSER- SECTION 301.15.
 PLEASE NOTE THE SUBMITTAL FOR THE ALUMSTAND HAS
 ILLEGIBLE PRINT THAT IS TOO SMALL TO READ AND SCAN INTO
 THE BUILDING DEPARTMENT RECORDS.
 J) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 PLANS- SECTION 307.
 2) PLEASE NOTE THAT AN ELECTRICAL PLAN AND SUB-PERMIT
 WILL BE REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  