Plan Review Notes
Plan Review Notes For Permit 15120203
Permit Number 15120203
Review Stop P
Sequence Number 1
Notes
Date Text
2015-12-12 06:49:081ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1.SHEET C8.1 SHOW SIZING CALCULATIONS FOOR DECK DRAINS.
 PER WPB AMEND. SEC 107.2.1
 2.P1 THE SANITARY PLAN DOES NOT MATCH THE RISER DIAGRAM
 PLEASE CORRECT .PER WPB AMEND. TO FBC SEC 107.2.1
 3.SHEET A-3.0 ACCESSORY SCHEDULE G BAR 1+2 NOT CORRECT
 PER FBC ACC SCE 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
 4 SHEET A- 3.0 SHOW THE CENTERLINE OF THE WATER CLOSET
 SHALL BE 16 INCHES (405 MM) MINIMUM TO 18 INCHES (455
 MM) MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC. SEC 604.2