Plan Review Notes For Permit 15120203 |
Permit Number |
15120203 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-12-12 06:49:08 | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | | | 1.SHEET C8.1 SHOW SIZING CALCULATIONS FOOR DECK DRAINS. | | PER WPB AMEND. SEC 107.2.1 | | 2.P1 THE SANITARY PLAN DOES NOT MATCH THE RISER DIAGRAM | | PLEASE CORRECT .PER WPB AMEND. TO FBC SEC 107.2.1 | | 3.SHEET A-3.0 ACCESSORY SCHEDULE G BAR 1+2 NOT CORRECT | | PER FBC ACC SCE 609.4 POSITION OF GRAB BARS. | | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, | | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) | | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF | | THE GRIPPING SURFACE, | | 4 SHEET A- 3.0 SHOW THE CENTERLINE OF THE WATER CLOSET | | SHALL BE 16 INCHES (405 MM) MINIMUM TO 18 INCHES (455 | | MM) MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC | | ACC. SEC 604.2 |
|