2016-01-27 11:57:09 | 15120203 | | 1517 CAMERON SAMUEL LN. | | POOL CABANA | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING | | MEANS. NEC 110.16, 110.22 | | PROVIDE GFCI PROTECTION FOR GENERAL PURPOSE RECEPTACLES | | IN CABANA. NEC 210.8 | | PROVIDE A INTERSYSTEM BONDING BAR AT EACH CABANA | | ELECTRICAL SERVICE. NEC 250 .94 | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | |
|