Plan Review Notes
Plan Review Notes For Permit 15120189
Permit Number 15120189
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-12-16 14:00:05PERMIT #15120189
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EVENT APPROVED WITH COMMENTS:
  
 1) TENT INSTALLATION REQUIRES A SEPERATE PERMIT. THIS
 PERMIT MUST BE OBTAINED NO LESS THAN 5 BUSINESS DAYS
 PRIOR TO THE EVENT. (IF USING A TENT COMPANY, HAVE THE
 TENT COMPANY APPLY FOR THE PERMIT.)
  
 2) ALL TENTS SHALL BE OF THE OPEN AREA/NO SIDEWALL
 TYPE, OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT
 SIGNS ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE
 FEET.
  
 3) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 4) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 5) PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE
 CANOPY MATERIAL.
  
 6) GENERATORS AND OTHER INTERNAL COMBUSTION POWER
 SOURCES SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5
 FEET AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
 7) A SITE WALK THROUGH MAY BE CONDUCTED BY A FIRE
 INSPECTOR, PRIOR TO THE START OF THE EVENT.
  
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  