Plan Review Notes For Permit 15120113 |
Permit Number |
15120113 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-12-02 14:26:51 | 1ST REVIEW 2010 MECHANICAL | | REVISION #15120113 | | PRIMARY #15030075 | | 12/2/15 | | | | 1) THE SUBMITTED PLAN TO INSTALL A 16 SEER 2.5- TON AC | | SYSTEM DOES NOT CORRELATE WITH THE ORIGINAL ENERGY | | CALCULATIONS WHICH INDICATE AN 18 SEER 5-TON SYSTEM TO | | BE INSTALLED. PLEASE PROVIDE THE FOLLOWING: A) REVISED | | ENERGY CALCULATIONS. B) AC COOLING AND HEATING | | CALCULATIONS. C) REVISED ELECTRICAL PLAN. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|