Plan Review Notes For Permit 15120094 |
Permit Number |
15120094 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-12-07 16:57:52 | APPROVED WITH CORRECTIONS AS FOLLOWS: PER NEC 430.52 | | THE OCPD FOR THIS FEEDER TO PROPERLY OPERATE THESE TWO | | MOTORS IS 40 AMP. IMPORTANT NOTICE: | | ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS | | PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL | | INSPECTOR. | | NO SITE TUBES WILL BE ACCEPTED | | |
|