Plan Review Notes For Permit 15120094
Permit Number 15120094
Review Stop E
Sequence Number 2
Notes
Date Text
2015-12-07 16:57:52APPROVED WITH CORRECTIONS AS FOLLOWS: PER NEC 430.52
 THE OCPD FOR THIS FEEDER TO PROPERLY OPERATE THESE TWO
 MOTORS IS 40 AMP. IMPORTANT NOTICE:
 ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS
 PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL
 INSPECTOR.
 NO SITE TUBES WILL BE ACCEPTED
  