2016-03-15 05:32:04 | 1)THE COMMENTS FROM THE PREVIOUS REVIEW HAVE NOT BEEN | | ADDRESSED. COMPLY WITH ALL PREVIOUS COMMENTS. | | 2) THE IRRIGATION LEGEND SHOWS A WILKINS #720-A | | BACKFLOW PREVENTER AND IT IS CALLED OUT AS AN RPZ. THIS | | DEVICE IS A PRESSURE VACUUM BREAKER, NOT AN RPZ. ALSO, | | YOU HAVE SUBMITTED COPIES OF THE END OF A BOX OR | | WHATEVER IT IS FOR A WATTS LF919QT BACKFLOW PREVENTER. | | THIS IS NOT A MANUFACTURER'S SPECIFICATION AS | | PREVIOUSLY REQUESTED. SUBMIT TWO COPIES OF COMPLETE | | MANUFACTURER'S SPECIFICATIONS FOR REVIEW. | | 3) THE BACKFLOW DEVICE MUST BE INSTALLED BY A PROPERLY | | LICENSED PLUMBING CONTRACTOR. SUBMIT AN APPLICATION BY | | A PLUMBING CONTRACTOR FOR THE INSTALLATION OF THIS | | DEVICE. F.S. 489.103. | | 4) INDICATE THE SIZE OF THE BACKFLOW PREVENTION DEVICE. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|