Notes |
Date |
Text |
2015-12-09 09:54:24 | 1ST REVIEW: FBC 2014 5TH ED 2011 NEC | | | | 1) PROVIDE ELECTRICAL PLANS TO INDICATE COMPLIANCE WITH | | THE NEC ARTICLE 600 AND THE FBC-EC405.2.4 . SEE BELOW: | | | | 2) ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING | | ? FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND | | INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS | | OTHERWISE APPROVED BY SPECIAL PERMISSION. 600.3 | | LISTING. | | | | 3) EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER | | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE | | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY | | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL | | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC | | 600.6(A)(1) | | | | 4) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC-EC405.2.4 | | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT | | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & | | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME | | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING | | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. | | FBC-EC405.2.4 | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|