Plan Review Notes For Permit 15120060 |
Permit Number |
15120060 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-12-07 10:35:13 | 1ST REVIEW 2014 MECHANICAL | | PERMIT #15120060 | | 12/7/15 | | | | 1) SHEET M1.1: PLEASE PROVIDE COMPLETE AC DUCT LAYOUT | | PLANS. THE PLAN IS INDICATING DUCTS SUPPLYING AIR TO A | | PORTION OF TENANT SPACE #1 HAVE BEEN CAPPED, HOWEVER | | THE ARCHITECTURAL PLANS INDICATE THE AREAS OF THE | | OFFICE POOL, AND WORK SPACES #1- 4, & 7 ETC. WILL BE | | OCCUPIED, AND NOT UNDER A SECOND PHASE. PLEASE CLARIFY | | AND SEE SECTION 309.1 FBC-14 MECHANICAL: A | | SPACE-HEATING SYSTEM IS REQUIRED FOR ALL OCCUPIED | | SPACES. | | 2) REFER TO SECTION 809.2 FBC-14 EXISITING BUILDING | | CODE AND SHOW COMPLIANCE: 809.2 ALTERED EXISTING | | SYSTEMS. | | IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL | | VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR | | EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER | | MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR | | AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION | | AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF | | VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY | | PROCEDURE OF ASHRAE 62. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|