2015-12-07 10:35:131ST REVIEW 2014 MECHANICAL
 PERMIT #15120060
 12/7/15
  
 1) SHEET M1.1: PLEASE PROVIDE COMPLETE AC DUCT LAYOUT
 PLANS. THE PLAN IS INDICATING DUCTS SUPPLYING AIR TO A
 PORTION OF TENANT SPACE #1 HAVE BEEN CAPPED, HOWEVER
 THE ARCHITECTURAL PLANS INDICATE THE AREAS OF THE
 OFFICE POOL, AND WORK SPACES #1- 4, & 7 ETC. WILL BE
 OCCUPIED, AND NOT UNDER A SECOND PHASE. PLEASE CLARIFY
 AND SEE SECTION 309.1 FBC-14 MECHANICAL: A
 SPACE-HEATING SYSTEM IS REQUIRED FOR ALL OCCUPIED
 SPACES.
 2) REFER TO SECTION 809.2 FBC-14 EXISITING BUILDING
 CODE AND SHOW COMPLIANCE: 809.2 ALTERED EXISTING
 SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  