2015-12-04 10:28:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET AO - INDICATES AND OCCUPANY LOAD OF SPACE # 1
 AS 42. SHEET A1.1 INDICATES AN OCCUPANY LOAD OF
 36+2+14= 52. PLEASE CORRECT.
  
 2. SHEET A 3.1 - WITHIN THE TRAINING ROOM (AN ASSEMBLY
 SPACE) IT INDICATES AN OCCUPANY LOAD OF 36, EQUALING
 THE CHAIR COUNT. NO DIMENSIONS OR OCCUPANY LOAD
 CLASSIFICATION CALCULATION ARE PROVIDED FOR THIS SPACE.
 PLEASE PROVIDE.
  
 3. SHEET 3.1 - DOOR # 5 MAYBE REQUIRED TO SWING IN THE
 DIRECTION OF EGRESS BASED ON THE SUBMITTAL INFORMATION
 OF # 2 ABOVE. PER SECTION NFPA 101, DOOR SWING
 DIRECTION, 7.2.1.4.2, DOOR IS REQUIRED TO SWING IN THE
 DIRECTION OF EGRESS TRAVEL FOR AN OCCUPANT LOAD OF 50
 OR GREATER PERSONS.
  
 4. SHEET A3.1 - DOOR # 3 SWING INTO THE EGRESS
 CORRIDOR. PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  