Plan Review Notes For Permit 15120060 |
Permit Number |
15120060 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-01-04 20:04:48 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6700 | | [email protected] | | ALTERNATE CONTACT | | MIKE ALBARRAN | | 561-805-6746 | | [email protected] | | | | | | PLEASE REFERENCE CURRENT CODE CYCLE NEC 2011 FBC 2014 | | SUSPENDED CEILINGS. FRAMING MEMBERS OF SUSPENDED | | CEILING SYSTEMS USED TO SUPPORT LUMINAIRES SHALL BE | | SECURELY | | FASTENED TO EACH OTHER AND SHALL BE SECURELY ATTACHED | | TO THE | | BUILDING STRUCTURE AT APPROPRIATE INTERVALS. LUMINAIRES | | SHALL | | BE SECURELY FASTENED TO THE CEILING FRAMING MEMBER BY | | MECHANICAL | | MEANS SUCH AS BOLTS, SCREWS, OR RIVETS. NEC 410.36 | | PLEASE SHOW SHORT-CIRCUIT RATING OF EQUIPMENT AND AIC | | RATING OF | | OCPD. NEC 110.9 , 110.10 | | |
|