Plan Review Notes
Plan Review Notes For Permit 15120030
Permit Number 15120030
Review Stop E
Sequence Number 1
Notes
Date Text
2015-12-08 12:39:17PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRIC
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE SIZE OF THE EXISTING ELECTRICAL PANEL.
 SUBMIT TWO COPIES OF A PANEL SCHEDULE WITH LOAD
 CALCULATIONS TO SHOW THAT THE EXISTING PANEL IS
 ADEQUATE FOR THE ADDITION LOADS OF THE ELECTRIC POOL
 HEATER AND OTHER POOL EQUIPMENT. FBC 107.2.1
  
 2) SUBMIT TWO SETS OF MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE POOL HEAT PUMP. FBC
 107.2.1