2016-02-20 03:42:421)THE PLAN SHOWS THE POOL WASTEWATER LINE DISCHARGING
 TO THE STORM SEWER. POOL WATER IS PROHIBITED FROM
 DISCHARGING TO THE STORM OR SANITARY SYSTEM PER CITY
 ORDINANCE # 90-126 (B) & 90-203 (A). SPECIFY WHERE THE
 WASTEWATER WILL DISCHARGE.3ND REQUEST.
 2) 2014 FBCB SEC. 454.1.5.4 REQUIRES VENTILATION IN THE
 EQUIPMENT ROOM. SUBMIT REQUIRED VENTILATION
 CALCULATIONS FOR REVIEW. 3ND REQUEST. THE PLAN NOTES
 "VENTILATION BY OTHERS." I NEED TO KNOW HOW COMPLIANCE
 WITH THIS CODE SECTION WILL BE MET.
 3) SUBMIT MSDS SHEETS FOR THE CHEMICALS IN THE PH TANK
 & CHEMICAL FEEDER.WPB SEC. 107.2.1.3RD REQUEST.
  
 I SUGGEST SETTING AN APPOINTMENT TO REVIEW THE PLAN
 REVIEW COMMENTS TO HELP GET THE PLUMBING APPROVED.
  