2016-01-27 05:40:521)THE PLAN SHOWS THE POOL WASTEWATER LINE DISCHARGING
 TO THE STORM SEWER. POOL WATER IS PROHIBITED FROM
 DISCHARGING TO THE STORM OR SANITARY SYSTEM PER CITY
 ORDINANCE # 90-126 (B) & 90-203 (A). SPECIFY WHERE THE
 WASTEWATER WILL DISCHARGE.2ND REQUEST.
 2) 2014 FBCB REQUIRES VENTILATION IN THE EQUIPMENT
 ROOM. SUBMIT REQUIRED VENTILATION CALCULATIONS FOR
 REVIEW. 2ND REQUEST
 3) SUBMIT MSDS SHEETS FOR THE CHEMICALS IN THE PH TANK
 & CHEMICAL FEEDER.WPB SEC. 107.2.1.
  