Plan Review Notes
Plan Review Notes For Permit 15120024
Permit Number 15120024
Review Stop P
Sequence Number 1
Notes
Date Text
2015-12-18 06:20:551) IDENTIFY THE MODEL OF THE GAS HEATER ON THE
 MANUFACTURER'S SPECIFICATION SHEET AND IF IT IS NATURAL
 OR LP GAS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. 3 OF 4 IN THE POOL SPECIFICATIONS INDICATES A
 FEATURE PUMP BUT NONE IS SHOWN ON THE PIPING DIAGRAM.
 CLARIFY.
 3) THE PLANS SHOW THE POOL WASTE LINE DISCHARGING TO
 THE SANITERY SEWER. POOL WATER IS PROHIBITED FROM
 DISCHARGING TO THE SANITARY OR STORM SYSTEMS PER CITY
 ORDINANCE 90-126 ( B ) (5) & 90-203 ( A).
 4) WHERE DOES THE FLOOR DRAIN TERMINATE? THE FLOOR
 DRAIN SHALL BE EQUIPPED WITH A TRAP PRIMER. SUBMIT A
 RISER DIAGRAM FOR THE SANITARY AND WATER LINES IN THE
 POOL EQUIPMENT ROOM. WPB AMEND. TO FBC SEC. 107.2.1.
 5) IDENTIFY THE FIXTURES IN THE POOL EQUIPMENT ROOM.
 THERE APPEARS TO BE A SINK AND A SERVICE SINK.CLARIFY.
 6) SUBMIT MANUF. SPECS. ON THE MAIN DRAIN AND THE
 SKIMMERS.
 7) SHT. 1 NOTES A 3 INCH WASTE LINE AND SHEET 4 IN THE
 POOL LEGEND SHOWS 1 1/2 INCH WASTE LINE. CLARIFY. WPB
 AMEND. TO FBC SEC. 107.2.1.
 8) INDICATE THE CAPACITY OF THE CL2 TANK AND THE PH
 TANK AND SUBMIT MSDS SHEETS FOR THE CHEMICALS.WPB
 AMEND. TO FBC SEC. 107.2.1.
 9) 2014 FBC SEC.454.1.5.4 REQUIRES VENTILATION IN THE
 EQUIPMENT ROOM. SUBMIT REQUIRED CALCULATIONS.
 10) PIPING AND INFLUENT, EFFLUENT AND BYPASS VALVES
 WHICH ALLOW ISOLATION OR REMOVAL OF THE HEATER FROM THE
 SYSTEM SHALL BE PROVIDED. 2014 FBC SEC.454.1.6.5.14.
 11) THE POOL HEATER SHALL BE EQUIPPED WITH A READILY
 ACCESSIBLE ON-OFF SWITCH THAT IS MOUNTED OUTSIDE THE
 HEATER TO ALLOW SHUTTING OF THE HEATER WITHOUT
 ADJUSTING THE THERMOSTAT. 2014 FBC-ENERGY SEC.C404.7.1.
 12) TIME SWITCHES OR OTHER CONTROL METHOD THAT CAN
 AUTOMATICALLY TURN OFF AND ON HEATERS AND PUMPS
 ACCORDING TO A PRESET SCHEDULE SHALL BE INSTALLED ON
 ALL HEATERS AND PUMPS. FBC-ENERGY SEC. C 404.7.2.
  