2016-05-18 11:28:024TH REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. FIRST SECTION OF GALVANIZED PIPE IS UNDERSIZED IT
 SHOULD BE 11/2IN. PER FBC FUEL GAS TABLE 402.4(5)
  
 2. THE SECTION OF CSST FROM SECOND BRANCH TO GALVANIZED
 AT EXTERIOR IS UNDERSIZED IT SHOULD BE 11/2IN PER FBC
 FUEL GAS TABLE 402.4(18)
  
 3. TABLE REFERENCED 402.4(20) IS FOR 1/2 POUND SYSTEM
 ITSHOULD BE TABLE 402.4(22) FOR 2LB. SYSTEM ALSO ADD
 TABLE 402.4(5) AND 402.4(18)
  
 4. SIZE PIPE DOWN STREAM OF STEPDOWN REGULATOR. PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 5.SUBMIT COMBUSTION AIR CALCULATIONS FOR THE RANGE ,
 FIRE PLACES AND GENERATOR IF ENCLOSED. PER FBC-2014
 FUEL GAS CODE SEC. 304.
  
 A GAS PLAN HAS NOT BEEN APPROVED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN APPROVED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
  
  
  
  