2016-04-26 11:39:58 | NEW SINGLE FAMILY RESIDENCE (R3), THIRD BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| |
| NOTE: BUILDING REVIEW MAY BE APPROVED WITH PROVISO ONCE |
| THE ENERGY CALCULATIONS ARE SIGNED. CONTRACTOR MAY |
| SUBMIT REQUIRED INFORMATION AFTER THE PERMIT IS ISSUED. |
| REVISION FEES MAY APPLY. CONTRACTOR TO ADVICE IF |
| PROVISO OPTION IS PREFERRED. |
| |
| 1- ENERGY CALCULATIONS SUBMITTED: |
| A) THE BUILDING'S OWNER/AGENT NEEDS TO CERTIFY |
| COMPLIANCE AT THE BOTTOM OF THE FORM SUBMITTED AS |
| REQUIRED BY SEC. R103.1.1.2 OF FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). (REPEATED COMMENT). |
| |
| B) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING |
| BUILDER NAME. SEC. R101.5.1.1.2 OF FBC - ENERGY |
| CONSERVATION, 5TH EDITION (2014). (REPEATED COMMENT). |
| |
| C) ROOF INFORMATION ON PAGE 2 OF 6 DOESN'T MATCH PLANS. |
| ROOF MATERIAL IS INCORRECT. SEC. R101.5.1.1.2 OF FBC - |
| ENERGY CONSERVATION, 5TH EDITION (2014). (REPEATED |
| COMMENT). |
| |
| ***NOTE: |
| LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL |
| BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING THE |
| DEFAULT FACTOR FOR GLAZING. |
| |
| 2- PROVIDE COMPLETE MANUFACTURER'S SPECS FOR ALL |
| FIREPLACES SHOWN ON PLANS. SHOWING COMPLIANCE WITH |
| CHAPTER 10 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| NOTE: DESIGNER OF RECORD TO REVIEW/APPROVE PRIOR TO |
| SUBMITTAL. |
| |
| 3- REVISE SPECIFICATIONS ON SECOND PARAGRAPH OF |
| HANDRAILS AND GUARDRAILS SECTION ON SHEET S9 TO COMPLY |
| WITH NOTE"F" OF TABLE R301.5 OF FBC-RESIDENTIAL. |
| (REPEATED COMMENT). |
| |
| 4- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R5 |
| SUBMITTED: PROVIDE SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR SELECTED ASSEMBLY W-55 AS REQUIRED BY |
| NOTE #8 ON PAGE 2 OF 76. NEED CALCULATIONS TO MEET THE |
| DESIGNER PRESSURES REQUIRED BY SEC. R301 |
| FBC-RESIDENTIAL. (REPEAT COMMENT). |
| |
| 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A)ENTRY DOOR AS SPECIFIED ON PLANS. DRAWING NO |
| "LAG-TEN" SUBMITTED DON'T CORRESPOND TO FLORIDA PRODUCT |
| APPROVAL COVER PAGE FL15911-R1 SUBMITTED. PROVIDE |
| DRAWINGS THAT WERE APPROVED WITH FL15911-R1 |
| |
| B) EXTERIOR DOORS: FRENCH DOORS WITH SIDELITES AS SHOWN |
| ON PLANS FOR DINING ROOM, GARAGE SWING DOOR, LAUNDRY |
| ROOM, CABANA BATHROOM AND CABANA STORAGE AS SHOWN ON |
| PLANS. (REPEAT COMMENT). |
| |
| 6- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT |
| APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |
| REMAINDER: SPECIAL INSPECTOR WILL BE REQUIRED FOR THE |
| INSPECTION OF THE SECOND FLOOR SLAB. SEC. 110.3.9 CITY |
| AMENDMENTS. PLEASE CONTACT KEN CONRAD (CHIEF BUILDING |
| INSPECTOR. (561)805-6666 OR [email protected]) ) FOR |
| DETAILS OF QUALIFIED INSPECTORS). |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD |
| DRAWINGS TO THE RE-SUBMITTED SET. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| (561)805-6712 |
| [email protected] |