2016-03-28 17:58:51 | NEW SINGLE FAMILY RESIDENCE (R3), ROOFING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) FLAT ROOF AS SPECIFIED ON PLANS. AND, CLEARLY |
| IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED. AND, |
| PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF |
| SELECTED ASSEMBLY DOESN'T MEET THE CALCULATED DESIGN |
| PRESSURES. |
| |
| RESPONSE: THE SELECTED ASSEMBLY (W-55) FROM FLORIDA |
| PRODUCT APPROVAL FL5680-R15 IS GOOD FOR -60PSF. NEED TO |
| PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR NAIL |
| ENHANCEMENT AT PERIMETER AND CORNER AREAS AS REQUIRED |
| BY NOTE #8 ON PAGE 2 OF 76 OF PRODUCT APPROVAL |
| SUBMITTED. |
| NOTE: FORM 100 SUBMITTED IS FOR PBC BUILDING |
| DEPARTMENT. THIS IS NOT USED BY THE CITY OF WPB. |
| |
| B) MODIFIED MEMBRANE THAT IS DESIGNED TO RECEIVE THE |
| FINISH MATERIAL SPECIFIED ON PLANS FOR THE TERRACES AND |
| BALCONIES. NOTE: CHECK DESIGN PRESSURES FOR SELECTED |
| ASSEMBLY. SIGNED AND SEALED RAS 117 CALCULATIONS MAY BE |
| REQUIRED. |
| |
| RESPONSE: ACCORDING TO CONDITIONS OF USE SEC. 5.2 OF |
| ICC ESR-2467 REPORT SUBMITTED, THIS PRODUCT IS FOR |
| INTERIOR USE ONLY. NEED PRODUCT APPROVAL FOR EXTERIOR |
| USE AND NEED TO CONSIDER THE WIND LOADS. |
| |
| 2- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT |
| APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |