Plan Review Notes
Plan Review Notes For Permit 15111032
Permit Number 15111032
Review Stop P
Sequence Number 2
Notes
Date Text
2016-03-18 16:47:26 
 PLUMBING COMMENTS;
  
 1.YOUR RESPONSE TO PREVIOUS COMMENT #2 DOES NOT COMPLY
 WITH CODE . WHERE YOU HAVE A HYDRAULIC ELEVATOR PIT YOU
 SHALL COMPLY WITH FBC PL SEC. 1003.4 OIL SEPARATORS
 REQUIRED.
 AT REPAIR GARAGES, CAR-WASHING FACILITIES, AT FACTORIES
 WHERE OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED AND
 IN HYDRAULIC ELEVATOR PITS, SEPARATORS SHALL BE
 INSTALLED INTO WHICH ALL OIL-BEARING, GREASE-BEARING OR
 FLAMMABLE WASTES SHALL BE DISCHARGED BEFORE EMPTYING
 INTO THE BUILDING DRAINAGE SYSTEM OR OTHER POINT OF
 DISPOSAL.
  
 EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN
 HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM
 IS INSTALLED.
  
 2. SHT.104 A RECIRCULATION SYSTEM IS REQUIRED TO COMPLY
 WITH FBC PL SEC. 607.2 HOT OR TEMPERED WATER SUPPLY TO
 FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER.
  
 3. SHT. P102 SOIL STACK FOR BATHROOMS 208+212 SHALL
 CONNECT TO BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP
 108 TO COMPLY WITH FBCR SEC. P3108.1
  
 4. SHT P104 THE COLD WATER MAIN SUPPLY APPEARS TO BE
 UNDERSIZED SHALL COMPLY WITH FBCR SEC. P2903
  
 5. SHT,P102 THE MODEL ON THE MANUFACTURE SPEC FOR
 TANKLESS HEATER DOES NOT MATCH THE ONE ON P104 PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  