Date |
Text |
2016-03-18 16:47:26 | |
| PLUMBING COMMENTS; |
| |
| 1.YOUR RESPONSE TO PREVIOUS COMMENT #2 DOES NOT COMPLY |
| WITH CODE . WHERE YOU HAVE A HYDRAULIC ELEVATOR PIT YOU |
| SHALL COMPLY WITH FBC PL SEC. 1003.4 OIL SEPARATORS |
| REQUIRED. |
| AT REPAIR GARAGES, CAR-WASHING FACILITIES, AT FACTORIES |
| WHERE OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED AND |
| IN HYDRAULIC ELEVATOR PITS, SEPARATORS SHALL BE |
| INSTALLED INTO WHICH ALL OIL-BEARING, GREASE-BEARING OR |
| FLAMMABLE WASTES SHALL BE DISCHARGED BEFORE EMPTYING |
| INTO THE BUILDING DRAINAGE SYSTEM OR OTHER POINT OF |
| DISPOSAL. |
| |
| EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN |
| HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM |
| IS INSTALLED. |
| |
| 2. SHT.104 A RECIRCULATION SYSTEM IS REQUIRED TO COMPLY |
| WITH FBC PL SEC. 607.2 HOT OR TEMPERED WATER SUPPLY TO |
| FIXTURES. |
| THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING, |
| FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT |
| REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET |
| (15 240 MM). RECIRCULATING SYSTEM PIPING AND |
| HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF |
| HOT OR TEMPERED WATER. |
| |
| 3. SHT. P102 SOIL STACK FOR BATHROOMS 208+212 SHALL |
| CONNECT TO BUILDING DRAIN DOWN STREAM OF BATHROOM GROUP |
| 108 TO COMPLY WITH FBCR SEC. P3108.1 |
| |
| 4. SHT P104 THE COLD WATER MAIN SUPPLY APPEARS TO BE |
| UNDERSIZED SHALL COMPLY WITH FBCR SEC. P2903 |
| |
| 5. SHT,P102 THE MODEL ON THE MANUFACTURE SPEC FOR |
| TANKLESS HEATER DOES NOT MATCH THE ONE ON P104 PLEASE |
| CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |