2016-03-28 18:30:32 | NEW SINGLE FAMILY RESIDENCE (R3), SECOND MECHANICAL |
| REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- RE-SUBMITTED SET OF PLANS IS MISSING DRAWINGS M201 |
| AND M301. NEED COMPLETE SET OF DRAWINGS. SEC. 107.2.1 |
| CITY AMENDMENTS. |
| |
| 2- MECHANICAL ENGINEER OF RECORD TO PROVIDE EQUIPMENT |
| SIZING CALCULATIONS AS REQUIRED BY SEC. R403.6.1 OF |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| RESPONSE: RESPONSE LETTER STATES THAT "SECTION R403 IS |
| NOT VALID CODE REFERENCE FOR ENERGY CODE". THIS IS |
| INCORRECT. SEE SEC. R403.6.1 OF FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| ALSO, THE ENGINEER IS CITING EXCEPTION #2 OF SEC. |
| R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014) TO DO A SUMMARY SHEET. THIS IS INCORRECT ALSO. |
| THE EXCEPTION #2 APPLIES TO ATTACHED SINGLE AND |
| MULTIPLE FAMILY UNITS ONLY. THIS IS A DETACHED SINGLE |
| FAMILY RESIDENCE. THEREFORE, NEED TO PROVIDE COMPLETE |
| EQUIPMENT SIZING CALCULATIONS USING AN APPROVED HEATING |
| AND COOLING CALCULATION METHODOLOGIES BASED ON THE |
| BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE |
| BUILDING AND PROVIDE THE MANUFACTURER AND MODEL NUMBER |
| OF THE OUTDOOR AND INDOOR UNITS AS REQUIRED BY SEC. |
| R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| 3- SHEET M302: UPDATE THE CODES AND STANDARDS |
| INFORMATION. THE CURRENT CODE IS THE FBC-RESIDENTIAL, |
| 5TH EDITION (2014) NOT 2010 FBC. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD |
| DRAWINGS TO THE RE-SUBMITTED SET. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |