Plan Review Notes For Permit 15111032 |
Permit Number |
15111032 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-03-23 11:08:29 | 2ND REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | GAS COMMENTS: | | | | 1. SHT. P103 SYSTEM IS INDICATED AS 2PSI PLEASE SHOW | | STEP DOWN REGULATORS FOR ALL APPLIANCES SHALL COMPLY | | WITH FBC FUEL GAS SEC. 410.1-410.2 | | 2. SHT. P103 PE PIPING IS NOT ALLOWED TO BE INSTALLED | | IN A STRUCTURE PER FBC FUEL GAS SEC. 404.17.1 | | 3.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | THE RESPONSE YOU GAVE ON FIRST REVIEW SEE P103 DOES NOT | | COMPLY | | 4.SHT. P103 SHOW LENGTH OF PIPE FROM METER TO FIRST | | BRANCH PER .FUEL GAS CODE SEC. 402.4.1. | | |
|