2016-03-23 11:08:292ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. SHT. P103 SYSTEM IS INDICATED AS 2PSI PLEASE SHOW
 STEP DOWN REGULATORS FOR ALL APPLIANCES SHALL COMPLY
 WITH FBC FUEL GAS SEC. 410.1-410.2
 2. SHT. P103 PE PIPING IS NOT ALLOWED TO BE INSTALLED
 IN A STRUCTURE PER FBC FUEL GAS SEC. 404.17.1
 3.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
 THE RESPONSE YOU GAVE ON FIRST REVIEW SEE P103 DOES NOT
 COMPLY
 4.SHT. P103 SHOW LENGTH OF PIPE FROM METER TO FIRST
 BRANCH PER .FUEL GAS CODE SEC. 402.4.1.
  