2016-03-17 18:38:43 | JOB PERMIT NUMBER: 15111032 |
| JOB ADDRESS: 2914 WASHINGTON RD |
| WEST PALM BEACH FLORIDA |
| DATE: MARCH 17 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT, |
| SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET |
| SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE |
| SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE |
| LOCATED WITHIN 25 FT. OF THE EQUIPMENT. MISSING ON |
| SHEET E100 BY CU#1 |
| - PROVIDE SERVICE EQUIPMENT LOCATION ON ELECTRICAL |
| FLOOR PLANS. WBA 107 |
| - GARAGE DOOR MOTOR OUTLET A 15 , A 17 MUST BE GFCI |
| PROTECTED NEC 210.8A |
| - GENERATOR ON A SEPARATE PERMIT TO INCLUDE CUT SHEETS |
| OF ATS EQUIPMENT ( SERVICE-RATED ) AND GENERATOR |
| MANUFACTURE SPECS. |
| - RISER DIAGRAM ON SHEET E102 STILL SHOWS SERVICE |
| GROUNDED CONDUCTOR BEING IN PARALLEL BY RUNNING A # 4 |
| AWG BONDING CONDUCTOR THIS IS A VIOLATION OF NEC 250 |
| GROUNDING & BONDING PLUS NEC 310.10 H WIRING METHODS. |
| - GROUNDING DETAIL TO INCLUDE INTERSYSTEM BONDING STRIP |
| NEC 250.94 |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |