2016-03-17 18:38:43JOB PERMIT NUMBER: 15111032
 JOB ADDRESS: 2914 WASHINGTON RD
 WEST PALM BEACH FLORIDA
 DATE: MARCH 17 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT,
 SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED WITHIN 25 FT. OF THE EQUIPMENT. MISSING ON
 SHEET E100 BY CU#1
 - PROVIDE SERVICE EQUIPMENT LOCATION ON ELECTRICAL
 FLOOR PLANS. WBA 107
 - GARAGE DOOR MOTOR OUTLET A 15 , A 17 MUST BE GFCI
 PROTECTED NEC 210.8A
 - GENERATOR ON A SEPARATE PERMIT TO INCLUDE CUT SHEETS
 OF ATS EQUIPMENT ( SERVICE-RATED ) AND GENERATOR
 MANUFACTURE SPECS.
 - RISER DIAGRAM ON SHEET E102 STILL SHOWS SERVICE
 GROUNDED CONDUCTOR BEING IN PARALLEL BY RUNNING A # 4
 AWG BONDING CONDUCTOR THIS IS A VIOLATION OF NEC 250
 GROUNDING & BONDING PLUS NEC 310.10 H WIRING METHODS.
 - GROUNDING DETAIL TO INCLUDE INTERSYSTEM BONDING STRIP
 NEC 250.94
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011