2015-12-04 11:38:27 | 1) SHT.H2 SHOWS STRUCTURAL DETAILS AND PLANS AND THESE |
| PLANS ARE SIGNED AND SEALED BY A LANDSCAPE ARCHITECT |
| WHICH VIOLATES FL. STATUTE 481.103. PLEASE CLARIFY. |
| 2) INDICATE ON THE PLANS IF THE ELEVATOR IS A TRACTION |
| TYPE OR A HYDRAULIC TYPE. IF OF A HYDRAULIC NATURE AND |
| THERE IS AN ELEVATOR PIT, THEN AN OIL SEPARATOR SHALL |
| BE REQUIRED. |
| 3) SUBMIT A WATER RISER FOR REVIEW PER WPB AMEND. TO |
| FBC SEC. 107.3.5.3. |
| 4) SHT. P 100 - SHOW THE CONTINUATION OF THE 3"SANITARY |
| LINE ON THE PLAN.WPB AMEND. TO FBC SEC. 107.2.1. |
| 5) CLEANOUTS ARE REQUIRED IN THE BASE OF THE STACKS TO |
| THE 2ND FLOOR. 2014 FBCR SEC.P3005.2.6. |
| 6) SUBMIT MANUF. SPECIFICATIONS FOR THE TANKLESS WATER |
| HEATERS..WPB AMEND. TO FBC SEC. 107.2.1. |
| 7) SHT. P100 - THERE IS A 3 INCH RISER TO THE 2ND FLOOR |
| IN THE DINING ROOM WALL ( RM.#119) THAT IS NOT SHOWN ON |
| THE SANITARY RISER. CLARIFY. |
| 8) CLEANOUTS ARE REQD. IN BOTH RISERS IN THE ISLAND |
| SINK. SEC. P3112 2014 FBCR. |
| 9) SHT. P102 - BATH 202 CANNOT DISCHARGE INTO THE VENT |
| STACK FOR POWDER ROOM 102. FBCR SEC. P3108.4. |
| 10) SHT. P102 - BATH 208 CANNOT DISCHARGE INTO THE VENT |
| STACK FOR BATH 108. FBCR SEC. P3108.4. |
| 11) SHT. P102 - BATH 220 - THE TUB AND WATER CLOSET ARE |
| NOT VENTED. 2014 FBCR SEC. P3201.2. |
| |