Plan Review Notes
Plan Review Notes For Permit 15111032
Permit Number 15111032
Review Stop P
Sequence Number 1
Notes
Date Text
2015-12-04 11:38:271) SHT.H2 SHOWS STRUCTURAL DETAILS AND PLANS AND THESE
 PLANS ARE SIGNED AND SEALED BY A LANDSCAPE ARCHITECT
 WHICH VIOLATES FL. STATUTE 481.103. PLEASE CLARIFY.
 2) INDICATE ON THE PLANS IF THE ELEVATOR IS A TRACTION
 TYPE OR A HYDRAULIC TYPE. IF OF A HYDRAULIC NATURE AND
 THERE IS AN ELEVATOR PIT, THEN AN OIL SEPARATOR SHALL
 BE REQUIRED.
 3) SUBMIT A WATER RISER FOR REVIEW PER WPB AMEND. TO
 FBC SEC. 107.3.5.3.
 4) SHT. P 100 - SHOW THE CONTINUATION OF THE 3"SANITARY
 LINE ON THE PLAN.WPB AMEND. TO FBC SEC. 107.2.1.
 5) CLEANOUTS ARE REQUIRED IN THE BASE OF THE STACKS TO
 THE 2ND FLOOR. 2014 FBCR SEC.P3005.2.6.
 6) SUBMIT MANUF. SPECIFICATIONS FOR THE TANKLESS WATER
 HEATERS..WPB AMEND. TO FBC SEC. 107.2.1.
 7) SHT. P100 - THERE IS A 3 INCH RISER TO THE 2ND FLOOR
 IN THE DINING ROOM WALL ( RM.#119) THAT IS NOT SHOWN ON
 THE SANITARY RISER. CLARIFY.
 8) CLEANOUTS ARE REQD. IN BOTH RISERS IN THE ISLAND
 SINK. SEC. P3112 2014 FBCR.
 9) SHT. P102 - BATH 202 CANNOT DISCHARGE INTO THE VENT
 STACK FOR POWDER ROOM 102. FBCR SEC. P3108.4.
 10) SHT. P102 - BATH 208 CANNOT DISCHARGE INTO THE VENT
 STACK FOR BATH 108. FBCR SEC. P3108.4.
 11) SHT. P102 - BATH 220 - THE TUB AND WATER CLOSET ARE
 NOT VENTED. 2014 FBCR SEC. P3201.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  