2015-12-30 19:04:35 | NEW SINGLE FAMILY RESIDENCE (R3), MECHANICAL REVIEW | | COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- MECHANICAL PLANS SUBMITTED DON'T PROVIDE ANY | | INFORMATION FOR THE FIREPLACES CHIMNEYS AND VENTS AS | | REQUIRED BY CHAPTER 18 OF FBC-RESIDENTIAL, 5TH EDITION | | (2014). MECHANICAL ENGINEER OF RECORD TO PROVIDE | | COMPLETE INFORMATION. | | | | 2- MECHANICAL ENGINEER OF RECORD TO PROVIDE EQUIPMENT | | SIZING CALCULATIONS AS REQUIRED BY SEC. R403.6.1 OF | | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | | | 3- SHEET M302: UPDATE THE CODES AND STANDARDS | | INFORMATION. THE CURRENT CODE IS THE FBC-RESIDENTIAL, | | 5TH EDITION (2014) NOT 2010 FBC. | | | | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD | | DRAWINGS TO THE RE-SUBMITTED SET. SUBMIT OLD DRAWINGS | | FOR REFERENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] | | | | | | |
|