Plan Review Notes
Plan Review Notes For Permit 15111032
Permit Number 15111032
Review Stop G
Sequence Number 1
Notes
Date Text
2015-12-04 12:56:481) THE GAS INSTALLATION SHALL BE DONE UNDER A SEPARATE
 PERMIT.
 2) INDICATE ON THE PLANS THE PSI OF THE GAS SYSTEM. IF
 IT IS A 2 PSI SYSTEM, SHOW THE LOCATION OF ALL THE
 REGULATORS ON THE PLAN.
 3) WHAT DOES THE TERM "ACTARIS B42" REPRESENT ON THE
 GAS RISER?
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL THE GAS
 APPLIANCES/EQUIPMENT. THE APPLIANCES/EQUIPMENT SHALL BE
 LISTED AND LABELED PER 2014 FBCR SEC. G2404.3.
 5) THE PLANS SHOW PE PIPE BEING INSTALLED UNDER THE
 STRUCTURE. PLASTIC PIPE SHALL BE INSTALLED OUTDOORS
 UNDERGROUND ONLY PER 2014 FBCR SEC. G2415.17.1.
 6) METAL PIPING IS NOT PERMITTED UNDERGROUND UNLESS
 APPROVED PROTECTIVE COATINGS OR WRAPPINGS ARE FACTORY
 APPLIED. ZINC COATINGS SHALL NOT BE DEEMED ADEQUATE
 PROTECTION FOR GAS PIPING UNDERGROUND. 2014 FBCR
 SEC.G2415.11.
 7) SUBMIT THE CORRESPONDING EHD NUMBER FOR THE CSST PER
 2014 FBCR SEC. G2413 SIZING TABLES.
 8) SHOW THE TOTAL BTU LOAD OF THE GAS SYSTEMS ON THE
 PLAN. WPB AMEND. TO FBC SEC. 107.3.5.3.
 9) SHOW THE LENGTH OF ALL SECTIONS OF GAS PIPE
 INCLUDING RISERS AND SHORT SECTIONS OF PIPE. WPB AMEND.
 TO FBC SEC. 107.3.5.3.
 10) THE BTU LOAD OF EACH OUTDOOR FIREPLACE SHALL BE ON
 THE GAS RISER DIAGRAM. WPB AMEND. TO FBC SEC.
 107.3.5.3.
 11) SHT. P103 REFERS TO TABLE 402.2 (20). THERE IS NO
 SUCH TABLE IN THE CODE. CLARIFY.
 12) THERE IS NO 170 FT. ROW IN THE GAS TABLES. THE ROW
 TO BE USED IS THE 175 FT. ROW.REVISE THE PLAN NOTE .
 13) THE GENERATOR SHALL BE UL2200 COMPLIANT.
  
 A THOROUGH GAS REVIEW COULD NOT BE ACCOMPLISHED DUE TO
 THE LACK OF THE ABOVE INFORMATION.
  