2016-01-04 17:54:14 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL |
| MARIO VALDES |
| ELECTRICAL PLAN EXAMINER |
| 516-805-6700 |
| [email protected] |
| ALTERNATE CONTACT |
| MIKE ALBARRAN |
| 561-805-6746 |
| [email protected] |
| |
| |
| GENERATOR ON SEPERATE PERMIT. POOL ON A SEPERATE |
| PERMIT. |
| FBC E C405.7.3.1 FEEDERS AND CUSTOMER OWNED SERVICE |
| CONDUCTORS. |
| FEEDER AND CUSTOMER OWNED SERVICE CONDUCTORS SHALL BE |
| SIZED FOR A MAXIMUM VOLTAGE DROP OF 2 PERCENT AT DESIGN |
| LOAD. |
| C405.7.3.2 BRANCH CIRCUITS. |
| BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM |
| VOLTAGE DROP OF 3 PERCENT AT DESIGN LOAD. |
| 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY |
| HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS |
| SHALL |
| BE PROVIDED PRIOR TO THE INSTALLATION OF THE FEEDERS. |
| SUCH A |
| DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF THE |
| BUILDING |
| OR OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL |
| CALCULATED |
| LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS |
| USED, THE CALCULATED LOAD AFTER APPLYING DEMAND |
| FACTORS, |
| AND THE SIZE AND TYPE OF CONDUCTORS TO BE USED. |
| SHEET E 102 SHOWS A 2 INCH CONDUIT FOR 3 350 KCMIL |
| THATS INADEQUATE CHECK TABLE 9 AND ANNEX C |
| ALSO SHOWS A # 4 BONDING CONDUCTOR WHICH WOULD INDICATE |
| PARRELLELING GROUNDED CONDUCTOR VIOLATION OF |
| NEC 250 AND 300 WIRING METHODS. PLEASE SPECIFY |
| CONDUCTOR AND CONDUIT TYPE ON RISER DIAGRAM. ( PANEL B |
| , C , PE. ) |
| PLEASE SHOW SERVICE EQUIPMENT ON SITE / FLOOR PLANS |
| PROVIDE STEAMER AND ELEVATOR SPECS DON'T SEE ON PANEL |
| SCHEDULE ? |
| SUB PANEL PE IS MARKED AS CIRCUIT 19 , 21 DOESN'T |
| CORRESPOND WITH PANEL SCHEDULE 33, 35 ? |
| |
| |
| 406.12 TAMPER-RESISTANT RECEPTACLES FOR DWELLING UNITS. |
| IN ALL AREAS SPECIFIED IN 210.52, ALL NONLOCKING-TYPE |
| 125-VOLT, 15- AND 20-AMPERE RECEPTACLES SHALL BE LISTED |
| TAMPER-RESISTANT RECEPTACLES. |
| 210.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| (A) DWELLING UNITS. ALL 120-VOLT, SINGLE PHASE, 15- AND |
| 20-AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED |
| IN |
| DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| RECREATION |
| ROOMS, CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS |
| SHALL |
| BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER, |
| COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF |
| THE |
| BRANCH CIRCUIT. |
| SMOKE ALARMS / CARBON MONOXIODE REQUIRED PER |
| RESIDENTIAL CODE SECTIONS 314 / 315 |
| FBC ER C405 75 % OF LIGHTING SHALL BE HIGH EFFICIENCY . |
| ALL RECCESSED FIXTURE SHALL BE |
| IC RATED AND SEALED TYPE. |
| GARARGE DOOR OPENERS AREN'T GFCI PROTECTED NEC 210.8 |
| NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN |
| 25? OF MECHANICAL EQUIPMENT. |
| DISCONNECTS FOR COMPRESSOR UNITS SEEM TO BE BEHIND |
| EQUIPMENT NEC 110.26 WORKING SPACE CLEARANCE. |
| |
| |