Plan Review Notes
Plan Review Notes For Permit 15111032
Permit Number 15111032
Review Stop E
Sequence Number 1
Notes
Date Text
2016-01-04 17:54:141ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 GENERATOR ON SEPERATE PERMIT. POOL ON A SEPERATE
 PERMIT.
 FBC E C405.7.3.1 FEEDERS AND CUSTOMER OWNED SERVICE
 CONDUCTORS.
 FEEDER AND CUSTOMER OWNED SERVICE CONDUCTORS SHALL BE
 SIZED FOR A MAXIMUM VOLTAGE DROP OF 2 PERCENT AT DESIGN
 LOAD.
 C405.7.3.2 BRANCH CIRCUITS.
 BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 VOLTAGE DROP OF 3 PERCENT AT DESIGN LOAD.
 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS
 SHALL
 BE PROVIDED PRIOR TO THE INSTALLATION OF THE FEEDERS.
 SUCH A
 DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF THE
 BUILDING
 OR OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL
 CALCULATED
 LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS
 USED, THE CALCULATED LOAD AFTER APPLYING DEMAND
 FACTORS,
 AND THE SIZE AND TYPE OF CONDUCTORS TO BE USED.
 SHEET E 102 SHOWS A 2 INCH CONDUIT FOR 3 350 KCMIL
 THATS INADEQUATE CHECK TABLE 9 AND ANNEX C
 ALSO SHOWS A # 4 BONDING CONDUCTOR WHICH WOULD INDICATE
 PARRELLELING GROUNDED CONDUCTOR VIOLATION OF
 NEC 250 AND 300 WIRING METHODS. PLEASE SPECIFY
 CONDUCTOR AND CONDUIT TYPE ON RISER DIAGRAM. ( PANEL B
 , C , PE. )
 PLEASE SHOW SERVICE EQUIPMENT ON SITE / FLOOR PLANS
 PROVIDE STEAMER AND ELEVATOR SPECS DON'T SEE ON PANEL
 SCHEDULE ?
 SUB PANEL PE IS MARKED AS CIRCUIT 19 , 21 DOESN'T
 CORRESPOND WITH PANEL SCHEDULE 33, 35 ?
  
  
 406.12 TAMPER-RESISTANT RECEPTACLES FOR DWELLING UNITS.
 IN ALL AREAS SPECIFIED IN 210.52, ALL NONLOCKING-TYPE
 125-VOLT, 15- AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
 210.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 (A) DWELLING UNITS. ALL 120-VOLT, SINGLE PHASE, 15- AND
 20-AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED
 IN
 DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATION
 ROOMS, CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS
 SHALL
 BE PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER,
 COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF
 THE
 BRANCH CIRCUIT.
 SMOKE ALARMS / CARBON MONOXIODE REQUIRED PER
 RESIDENTIAL CODE SECTIONS 314 / 315
 FBC ER C405 75 % OF LIGHTING SHALL BE HIGH EFFICIENCY .
 ALL RECCESSED FIXTURE SHALL BE
 IC RATED AND SEALED TYPE.
 GARARGE DOOR OPENERS AREN'T GFCI PROTECTED NEC 210.8
 NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 25? OF MECHANICAL EQUIPMENT.
 DISCONNECTS FOR COMPRESSOR UNITS SEEM TO BE BEHIND
 EQUIPMENT NEC 110.26 WORKING SPACE CLEARANCE.
  
  