2015-12-29 11:31:27NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- NEED A SEPARATE DEMOLITION PERMIT TO DEMOLISH
 EXISTING HOUSE. SEC. 105.1 CITY AMENDMENTS.
  
 2- PROVIDE SOIL TEST REPORT. 2 COPIES. SEC. R401.4 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- PROVIDE ENERGY CALCULATIONS. SEC. R101.5 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE WITH PLANS SUBMITTED TO AVOID
 CONFLICTS OR DELAYS.
  
 5- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 6-REVISE OCCUPANCY AND BUILDING TYPE INFORMATION ON THE
 COVER SHEET. THIS HOUSE IS NOT CONSTRUCTION TYPE III.
 SINGLE FAMILY RESIDENCES ARE TYPICALLY CONSTRUCTION VA
 OR VB. CONSTRUCTION TYPE III REQUIRES 2 HOUR WALLS. SEE
 TABLE 601 OF FBC-BUILDING, 5TH EDITION (2014). REVISE
 AS REQUIRED.
  
 7- A) PROPERTY IS LOCATED IN FLOOD ZONE A5. PROVIDE
 COMPLETE INFORMATION SHOWING COMPLIANCE WITH THE FLOOD
 RESISTANT CONSTRUCTION OF SEC. R322 OF FBC-RESIDENTIAL,
 5TH EDITION (2014). PROVIDE SURVEY WITH FINISH FLOOR
 ELEVATIONS AND SPECIFY ON PLANS (ARCHITECTURAL AND
 STRUCTURAL) THE FINISHED FLOOR ELEVATION FOR MAIN
 HOUSE, GARAGE, CABANA AND ALL EQUIPMENT. PROVIDE
 COMPLETE SPECIFICATIONS FOR FLOOD RESISTANT
 CONSTRUCTION FOR AREAS THAT ARE BELOW THE 7'-6" (FLOOD
 ZONE A5 HAS A BASE FLOOD ELEVATION OF 7'-0". CITY
 ORDINANCE REQUIRES FINISH FLOOR TO BE 6" ABOVE THE BASE
 FLOOD ELEVATION).
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE ENCLOSED AREA BELOW THE DESIGN
 FLOOD ELEVATION SHOWING COMPLIANCE WITH ALL THE
 REQUIREMENTS OF SEC. R322.2.2 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
 NOTE: SEE REQUIRED LOCATION OF VENTS. ALSO, TAKE INTO
 CONSIDERATION VENTS FOR THE CARPORT AREA. THIS AREA IS
 ENCLOSED ON THREE SIDES.
  
 C) NOTE: ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION. ELEVATION CERTIFICATE SUBMITTED IS FOR
 THE EXISTING HOUSE. NEW ELEVATION CERTIFICATES REQUIRED
 FOR THE PROPOSED HOUSE, GARAGE, CABANA AND ALL THE
 EQUIPMENT.
  
 8- ENTRY DOOR DOESN'T COMPLY WITH SEC. R311.2 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). DOOR LEAF NEEDS TO
 PROVIDE 32" CLEAR OPENING.
  
 9- BATHROOM DOOR IN THE GUEST ROOM ON FIRST FLOOR
 DOESN'T COMPLY WITH SEC. R320 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014). DOOR NEEDS TO PROVIDE 29" CLEAR
 OPENING.
  
 10- ATTIC ACCESS LOCATED IN THE GUEST ROOM ABOVE THE
 GARAGE DOESN'T COMPLY WITH SEC. R807 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). SIZE IS TOO SMALL
 AND THE LOCATION INSIDE THE CLOSET IS NOT ALLOWED. IT'S
 GOING TO BE BLOCKED BY SHELVES AND ANYTHING PLACED IN
 THE CLOSET.
  
 11- ENTRY DOOR FOR GUEST ROOM ABOVE THE GARAGE DOESN'T
 COMPLY WITH SEC. R311.2 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014). DOOR LEAF NEEDS TO PROVIDE 32" CLEAR OPENING.
  
 12- PROVIDE ATTIC ACCESS IN CABANA. SEC. R807 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 13- NEED TO SPECIFY CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH BEDROOM AS REQUIRED BY SEC. R315 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). INCLUDE FIRST
 FLOOR GUEST-ROOM AND SECOND FLOOR GUEST ROOM ABOVE
 GARAGE.
  
 14- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING
 AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS.
  
 15- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE
 INSULATION SPECIFIED ON PLANS. DESIGNER OF RECORD TO
 REVIEW AND APPROVE IT PRIOR TO SUBMITTAL TO THIS
 OFFICE. SEC. R316 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 16- WALL SECTION AT GARAGE S-5/A302: PROVIDE
 SPECIFICATIONS FOR THE INSULATION BETWEEN GARAGE AND
 SECOND FLOOR GUEST-ROOM. COORDINATE WITH ENERGY
 CALCULATIONS. SEC. R103.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 17- PROVIDE COMPLETE WALL SECTIONS AND SPECIFICATIONS
 FOR ALL 5 FIREPLACES SHOWN ON PLANS SHOWING COMPLIANCE
 WITH CHAPTER 10 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 PROVIDE COMPLETE MANUFACTURER'S SPECS FOR EACH ONE.
 NOTE: DESIGNER OF RECORD TO APPROVE ALL MANUFACTURER'S
 SPECS PRIOR TO SUBMITTAL. CLARIFY IF FACTORY BUILT
 FIREPLACES?. CLARIFY IF FACTORY BUILT CHIMNEYS?.
 SPECIFY ALL CLEARANCES AND CHIMNEY'S TERMINATION, ETC.
 NOTE: COORDINATE WITH MECHANICAL COMMENTS. CHIMNEYS AND
 VENTS AS REQUIRED BY CHAPTER 18 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 18- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 HANDRAILS AND GUARDRAILS SHOWING COMPLIANCE WITH THE
 LIVE LOAD REQUIREMENTS OF TABLE R301.5 AND THE ALL
 REQUIREMENTS OF SEC. R311.7.8 AND SEC. R312 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 19- NOTE: SPECIAL INSPECTOR WILL BE REQUIRED FOR THE
 INSPECTION OF THE SECOND FLOOR SLAB. SEC. 110.3.9 CITY
 AMENDMENTS. PLEASE CONTACT KEN CONRAD (CHIEF BUILDING
 INSPECTOR. (561)805-6666 OR [email protected]) ) FOR
 DETAILS OF QUALIFIED INSPECTORS).
  
 20- SEC. R803.2.3.1 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014) REQUIRES 8D RING SHANK NAILS. NAILS SPECIFIED ON
 DETAIL 12/S7 ARE NO SPECIFIED AS RING SHANK NAILS.
 CLARIFY IF USING RING SHANK NAILS OR NOT. IF NOT USING
 RING SHANK NAILS, THEN PROVIDE CALCULATIONS SHOWING
 THAT THE 10D NAILS ARE EQUIVALENT OR BETTER THAN THE
 REQUIRED 8D RING SHANK NAILS. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 21- STRUCTURAL PLANS TO SPECIFY THE ATTIC LIVE LOAD AS
 REQUIRED BY FOOTNOTES "B" AND "G" OF TABLE R301.5 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 22- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE PERGOLA, MASTER TERRACE AND GUEST
 TERRACE TRELLIS. SEC. R301 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
  
 23- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILE AS SPECIFIED ON PLANS.
  
 B) ROOF TILE ADHESIVE, IF SPECIFIED BY THE DESIGNER OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 C) FLOOD VENTS AS SPECIFIED ON PLANS.
  
 D) FLAT ROOF AS SPECIFIED ON PLANS. AND, CLEARLY
 IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED. AND,
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE CALCULATED DESIGN
 PRESSURES.
  
 E) MODIFIED MEMBRANE THAT IS DESIGNED TO RECEIVE THE
 FINISH MATERIAL SPECIFIED ON PLANS FOR THE TERRACES AND
 BALCONIES. NOTE: CHECK DESIGN PRESSURES FOR SELECTED
 ASSEMBLY. SIGNED AND SEALED RAS 117 CALCULATIONS MAY BE
 REQUIRED.
  
 F) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 G) ENTRY DOOR AS SPECIFIED ON PLANS.
  
 H) GARAGE DOORS AS SPECIFIED ON PLANS.
  
 I) ALL EXTERIOR DOORS AS SPECIFIED ON PLANS. AND,
 CLEARLY IDENTIFY LOCATION. FOR EXAMPLE, CABANA DOOR,
 GARAGE DOOR, LAUNDRY DOOR, STORAGE DOOR, ETC.
  
 J) ALL WINDOWS AS SPECIFIED ON PLANS.
  
 24- DESIGNER OF RECORD TO APPROVE ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED SHEET. DON'T STAPLE OLD
 DRAWINGS TO THE RE-SUBMITTED SET. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  