Plan Review Notes
Plan Review Notes For Permit 15111025
Permit Number 15111025
Review Stop E
Sequence Number 1
Notes
Date Text
2015-12-03 14:26:021ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
  
 600.6 DISCONNECTS. EACH SIGN AND OUTLINE LIGHTING
 SYSTEM,
 FEEDER CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN,
 OUTLINE
 LIGHTING SYSTEM, OR SKELETON TUBING SHALL BE CONTROLLED
 BY AN
 EXTERNALLY OPERABLE SWITCH OR CIRCUIT BREAKER THAT
 OPENS ALL
 UNGROUNDED CONDUCTORS AND CONTROLS NO OTHER LOAD. THE
 SWITCH OR CIRCUIT BREAKER SHALL OPEN ALL UNGROUNDED
 CONDUCTORS
 SIMULTANEOUSLY ON MULTI-WIRE BRANCH CIRCUITS IN
 ACCORDANCE
 WITH 210.4(B). SIGNS AND OUTLINE LIGHTING SYSTEMS
 LOCATED WITHIN FOUNTAINS SHALL HAVE THE DISCONNECT
 LOCATED
 IN ACCORDANCE WITH 680.12.
  
 (1) WITHIN SIGHT OF THE SIGN. THE DISCONNECTING MEANS
 SHALL
 BE WITHIN SIGHT OF THE SIGN OR OUTLINE LIGHTING SYSTEM
 THAT IT
 CONTROLS. WHERE THE DISCONNECTING MEANS IS OUT OF THE
 LINE OF
 SIGHT FROM ANY SECTION THAT IS ABLE TO BE ENERGIZED,
 THE DISCONNECTING
 MEANS SHALL BE CAPABLE OF BEING LOCKED IN THE OPEN
 POSITION. THE PROVISION FOR LOCKING OR ADDING A LOCK TO
 THE
 DISCONNECTING MEANS MUST REMAIN IN PLACE AT THE SWITCH
 OR
 CIRCUIT BREAKER WHETHER THE LOCK IS INSTALLED OR NOT.
 PORTABLE
 MEANS FOR ADDING A LOCK TO THE SWITCH OR CIRCUIT
 BREAKER SHALL
 NOT BE PERMITTED.
  
  
 ENERGY CODE SECTION C 504
 FBC-EC 505.2.4 - PROVIDE A TIME CLOCK OR ASTRONOMICAL
 SWITCH TO TURN OFF DURING DAYLIGHT HOURS
  