2015-12-16 18:01:26 | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| 1. ELECTRICAL SPECIFICATIONS SECTION ON SHEET E0.1 |
| MISQUOTED FBC-E SECTIONS: FBC-EC405.7.3 VOLTAGE DROP. |
| FEEDERS & CUSTOMER OWNED SERVICE CONDUCTORS SHALL BE |
| SIZED FOR A MAXIMUM OF 2% VOLTAGE DROP. BRANCH CIRCUITS |
| SHALL BE SIZED FOR A MAXIMUM OF 3% VOLTAGE DROP. |
| 2. TRENCHING FOR FPL CONDUCTORS BETWEEN EXISTING POLE |
| AND THE PROPOSED FPL TRANSFORMER, IF UNDER THE SCOPE OF |
| THIS PERMIT, AS WELL AS ALL OTHER UNDERGROUND WIRING |
| SHALL REMAIN OPEN FOR INSPECTION UNLESS PRIOR |
| ARRANGEMENTS ARE MADE WITH ELECTRICAL INSPECTOR, OR RUN |
| VIA DIRECT BORING. SHEET E2.1 |
| 3. FBC 1006.1 MEANS OF EGRESS ILLUMINATION REQUIRED. |
| THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE, |
| SHALL BE ILLUMINATED AT ALL TIMES THE BUILDING SPACE |
| SERVED BY THE MEANS OF EGRESS ARE OCCUPIED. SHEET E2.1 |
| 4. THE SERVICE RACK SHALL BE GUARDED AGAINST PHYSICAL |
| DAMAGE AS INDICATED IN NEC 110.27(B). SHEET E2.1 |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |