Plan Review Notes For Permit 15110971 |
Permit Number |
15110971 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-12-01 12:50:46 | PERMIT #15110971 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | 1) A SEPERATE PERMIT IS REQUIRED FOR THE INSTALLATION | | OF A TENT. YOUR SELECTED TENT COMPANY WILL NEED TO | | APPLY FOR THIS PERMIT NO LESS THAN 5 BUSINESS DAYS | | PRIOR TO THE EVENT DATE. | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | BUILDING STRUCTURES. | | | | TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | LOCATIONS. | | | | PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR THE CANOPY | | MATERIAL. | | | | GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES | | SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET | | AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR | | ENCLOSURE. | | | | | | | | SUE ELLEN CALDERON | | ASST. FIRE MARSHAL | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 804-4751 | | |
|