Plan Review Notes For Permit 15110873 |
Permit Number |
15110873 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2016-04-08 09:15:17 | 4TH REVIEW: FBC 2014 MECHANICAL | | PERMIT #15110873 | | 4/8/16 | | | | 1) THE PREVIOUS REVIEW COMMENTS STILL EXIST: A) | | INDICATE THE REQUIRED 30' CLEARANCE DISTANCE FROM THE | | EXHAUST OUTLET TO THE PROPERTY LINE AT THE EAST OF THE | | BUILDING. B) A CUT SHEET FOR A PORTABLE EXTENSION | | LADDER HAS BEEN SUBMITTED, HOWEVER AS NOTED IN THE | | PREVIOUS REVIEW, A PERMANENT LADDER IS REQUIRED- PLEASE | | SEE SECTION 306.5 AND REVISE THE PLANS TO SHOW | | COMPLIANCE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|