Plan Review Notes
Plan Review Notes For Permit 15110873
Permit Number 15110873
Review Stop M
Sequence Number 4
Notes
Date Text
2016-04-08 09:15:174TH REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110873
 4/8/16
  
 1) THE PREVIOUS REVIEW COMMENTS STILL EXIST: A)
 INDICATE THE REQUIRED 30' CLEARANCE DISTANCE FROM THE
 EXHAUST OUTLET TO THE PROPERTY LINE AT THE EAST OF THE
 BUILDING. B) A CUT SHEET FOR A PORTABLE EXTENSION
 LADDER HAS BEEN SUBMITTED, HOWEVER AS NOTED IN THE
 PREVIOUS REVIEW, A PERMANENT LADDER IS REQUIRED- PLEASE
 SEE SECTION 306.5 AND REVISE THE PLANS TO SHOW
 COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  