Plan Review Notes For Permit 15110873 |
Permit Number |
15110873 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-03-31 10:20:27 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #15110873 | | 3/31/16 | | | | 1) COMMENT #2G FROM THE 1ST REVIEW STILL EXISTS. THE | | 30" REQUIRED CLEARANCE FOR THE SPRAY EXHAUST TO THE | | EAST PROPERTY LINE IS NOT SHOWN. | | 2) REFER TO SECTION 306.5 FBC-14 MECHANICAL AND | | INDICATE HOW SERVICE ACCESS WILL BE PROVIDED TO THE | | SPRAY EXHAUST DUCT TERMINATION ON THE ROOF. WILL A | | PERMANENT ROOF LADDER BE INSTALLED? PROVIDE DETAILS IF | | APPLICABLE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|